OUC (external)
Any partner
Passive TCP/IP connection
With an TCP/IP connection where you are only receiving and not sending data, you will not be informed about a loss of
connection.
26
Special features
Via PC communication interface
Supported communication methods
•
–
TCP programmed
–
UDP programmed
–
Note: Secure OUC communication is not possible over the PC communication
interface.
Addressing of the external partner via the CPU
•
–
HW ID: 59 (PC communication interface)
–
IP address: IP address of the external partner
–
Port number: As defined
Addressing the CPU via external partner
•
–
IP address: IP address of the connected Windows Ethernet interfaces
–
Port number: As defined
Via runtime communication interface
Supported communication methods
•
–
TCP programmed
–
UDP programmed
–
ISOonTCP programmed
With IP Routing or NAT Routing set up under Windows
•
–
Addressing of the external partner via the CPU
HW ID: 0
IP address: IP address of the external partner
Port number: As defined
–
Addressing the CPU via external partner
IP address: Runtime communication interface
Port number: As defined
With port forwarding set up under Windows
•
–
Addressing of the external partner via the CPU
HW ID: 0
IP address: IP address of the Siemens RT-VMM network adapter
Port number: As defined
–
Addressing the CPU via external partner
IP address: IP address of the connected Windows Ethernet interfaces
Port number: As defined
Add-ons to CPU 1505SP (F/T/TF), CPU 1507S (F), CPU 1508S (F) Version 2.6
A5E45929273-AD, 07/2019