24
Special features
Can be configured over any Windows Ethernet interface
Special features
Configuration in STEP 7 including connection configuration (S7 routed connection)
Configuration in STEP 7 including connection configuration (S7 routed connection)
Configuration in STEP 7 including connection configuration (S7 routed connection)
see application example
(https://support.industry.siemens.com/cs/ww/en/view/109750290)
Via unspecified connection
Requirement
•
–
You have enabled "PUT/GET".
Addressing
•
–
IP address: Windows interface in use
–
Rack = 0; slot = index
Special features
Configuration in STEP 7 including connection configuration (S7 connection)
Special features
Configuration in STEP 7 including connection configuration (add S7 routed
connection)
Configuration in STEP 7 including connection configuration (add S7 routed
connection)
Configuration in STEP 7 including connection configuration (add S7 routed
connection)
Not supported
Not supported
Not supported
Special features
Supported communication methods
•
–
Data access to non-optimized data
Requirement
•
–
You have enabled "PUT/GET".
–
The index of the CPU is 1.
Addressing of the external partner via the CPU
•
–
Not supported
Addressing the CPU via the external partner
•
–
IP address: IP address of one of the Windows Ethernet interfaces
–
Port number: 102
–
Rack = 0, slot = set index = 1
Add-ons to CPU 1505SP (F/T/TF), CPU 1507S (F), CPU 1508S (F) Version 2.6
A5E45929273-AD, 07/2019