1 - First set DIP 2 to ON (LED DL1 flashes quickly) and after DIP1 to ON (LED DL1 flashes slowly).
2 - Press the PED pedestrian button. or the remote control button dedicated to the pedestrian
opening (if previously programmed) => The gate opens.
3 - Press the pedestrian button PED. to stop the run (thus defining the opening of the gate).
4 - Press the pedestrian button to start closing.
5 - When the closing limit switch is reached, reset DIP1 and 2 to OFF.
During programming, the safety devices are active and their intervention stops the
programming (the LED from blinking remains lit steadily and the buzzer sounds for 10 s).
To repeat the programming position the DIP 1 and DIP 2 to OFF, close the gate and repeat the
procedure described above.
F - RADIO CODES PROGRAMMING PROCEDURE FOR TOTAL OPENING (1000 CODES
MAX) - with radio module ACG8069
ATTENTION: before storing the radio codes, use DIP 12 to select which transmitters to use:
DIP 12 OFF: SUN-PRO variable code transmitters can be memorized:
SUN-PRO 2CH 2-channel - red keys and white led cod. ACG6210
SUN-PRO 4CH 4-channel - red keys and white led cod. ACG6214
DIP 12 ON (by factory): You can store transmitters with fixed code SUN:
SUN 2CH 2-channel - blue keys and white led cod. ACG6052
SUN 4CH 4-channel - blue keys and white led cod. ACG6054
SUN CLONE 2CH 2-channel - blue keys and yellow led cod. ACG6056
SUN CLONE 4CH 4-channel - blue keys and yellow led cod. ACG6058
ATTENTION: it is not possible to memorize at the same time transmitters with fixed code and
transmitters with variable code.
Programming can be done only when the gate is stationary.
1 - First set DIP 1 to ON and then DIP 2 to ON. The LED DL12 flashes red for 10 s.
2 - Press the TRANSMITTER button (usually channel A) within the allotted 10 s. If the remote
is memorized properly LED DL12 blinks green and a buzzer tone confirms the correct
memorization. The 10 s for programming the codes are automatically renewed, with LED
DL12 which flashes red, in order to store the next transmitter.
3 - To finish programming, wait 10 s, or press the PROG button briefly. LED DL12 stops flashing.
4 - Re-set DIP 1 to OFF and DIP 2 to OFF.
ALL RADIO CODES FOR TOTAL OPENING CANCELLATION PROCEDURE
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - LED DL12 flashes red for 10 s.
3 - Press and hold the PROG button for 5 s. Memory cancellation is indicated by two green
flashes of LED DL12 and 2 tones of the buzzer.
4 - LED DL12 flashes red again for 10 seonds and you can add new codes as shown above.
5 - Re-set DIP 1 to OFF and DIP 2 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR TOTAL OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The LED DL12 flashes green 6 times when the memory is full (1000 codes). Now LED DL12
blinks red for 10 s enabling possible cancellation of all codes.
3 - Re-set DIP 1 to OFF and DIP 2 to OFF.
G - RADIO CODES PROGRAMMING PROCEDURE FOR PEDESTRIAN OPENING (1000
CODES MAX) - with radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. DL12 flashes green for 10 s.
2 - Press the transmitter button (usually channel B) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks red and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes green) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
ALL RADIO CODES FOR PEDESTRIAN OPENING CANCELLATION PROCEDURE
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 s.
2 - Press and hold the PROG button for 5 s. Memory cancellation is indicated by two red flashes
of LED DL12 and two tones of the buzzer.
3 - The red LED DL1 remains active and you can add new codes as shown above.
4 - Reset DIP 1 to OFF and DIP 3 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR PEDESTRIAN OPENING)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
s enabling possible cancellation of codes.
3 - Set DIP 1 to OFF and DIP 3 to OFF.
H - PROGRAMMING RADIO CODES (FOR R-AUX RELAY) (1000 CODES MAX) - with
radio module ACG8069
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. DL12 flashes orange for 10 s.
2 - Press the transmitter button (usually channel C) within the allotted 10 s. If the transmitter
is properly memorized LED DL12 blinks green and the buzzer emits a tone. The 10 s are
automatically renewed (DL12 flashes orange) in order to memorize next transmitter.
3 - To finish programming wait 10 s, or press the PROG button briefly. The LED DL12 stops
flashing.
4 - Reset DIP 1, 2, 3 to OFF.
RADIO CODES CANCELLATION PROCEDURE (FOR R-AUX RELAY)
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON. LED DL12 flashes green for 10 s.
2 - During these 10 s press and hold the PROG button for 5 s. Memory cancellation is indicated
by two green flashes of LED DL12 and two tones of the buzzer.
3 - LED DL12 blinks orange again for 10 s and you can add new codes as shown above.
4 - Re-Set DIP 1, 2, 3 to OFF.
RADIO CODES MEMORY FULL INDICATOR (FOR R-AUX RELAY)
Indication is visible only when gate is stationary.
1 - Set DIP 1 to ON, DIP 2 to ON and then DIP 3 to ON.
2 - LED DL12 flashes green 6 times if the memory is full (1000 codes). LED DL12 blinks red for 10
s enabling possible cancellation of codes.
3 - Re-Set DIP 1, 2, 3 to OFF.
FUNCTIONING OF CONTROL ACCESSORIES
STEP-BY-STEP BUTTON (COM A+/START)
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
re-opens.
OPEN BUTTON (COM A+/OPEN)
The button controls the opening movement when the gate is stationary. If activated while
closing, it re-opens the gate.
B.I.O. BUTTON - OPENS WITH CLOCK FEATURE (COM A+/B.I.O.)
This function is useful during peak hours, when vehicle traffic is slow (e.g. entry/exit of
workers, emergencies in parking or residential areas and, temporarily, for moving operations).
By connecting a switch and/or a daily/weekly clock to COM A+/B.I.O., you can open and keep
the automation open for as long as the switch is pressed or the clock remains active. When the
gate is open, all the commands are ignored.
Releasing the switch or at the end of the set time, the automation closes immediately.
CLOSE BUTTON (COM A+/CLOSE)
Controls the closing movement when the gate is stationary.
TRANSMITTER
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
reopens.
PEDESTRIAN OPEN BUTTON (COM A+/PED.)
Partial opening and closing control.
During pedestrian opening, pausing or closing, you can control the opening of any command
linked to the L1 board.
With DIP 6 you can choose the operation mode of the pedestrian push button.
DIP 6 ON => It cyclically performs the commands open-stop-close-stop-open etc.
DIP 6 OFF => Opens the gate when closed. There is no effect if activated while opening. If
activated when gate is open, the gate closes. If activated while closing, the gate
reopens.