Connection
Turn input to the UPS ON
6
If the UPS is connected to a transformer, turn the transformer's Input and Output
Circuit Breakers ON.
Turn the UPS's Input Circuit Breaker ON.
Press the UPS's ON button until you hear a beep to begin inverter operation.
If your AC input is not providing power normally, you may "cold start" your UPS
from battery. (Your battery must be at least partially charged for this operation to
succeed.) Press and hold the "ON/OFF" switch until you hear a beep to start your
UPS in "ON BATTERY" mode. Note that some electronic equipment may draw
more amps during startup; when starting from battery, consider reducing the initial
load on the UPS.
Your UPS will perform a brief self-test and show the results on the LCD Display.
See the Self-Test section, pg. 12, for the display sequence.
Configure your UPS's output.
7
Put your UPS into Standby mode by holding the OFF button down until the UPS
beeps, then put your UPS into setup mode by holding down both of its scroll buttons at
once. Scroll through the setup options and select the appropriate setting for each of
the following options.
Output Voltage: Select 200, 208, 220, 230 or 240 VAC.
Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.
Economy Mode: Your UPS can provide on-line operation with zero transfer time.
It can also operate in a more energy-efficient line-interactive mode. Select
Economy On to put the UPS in line-interactive mode. Select Economy Off to put
the UPS in on-line mode.
Turn UPS output ON.
8
Turn the UPS's Output Circuit Breaker ON.
If the UPS is connected to a transformer, turn the transformer's Manual Bypass
Switch from BYPASS to NORMAL.
Your UPS will now provide power to connected equipment.
To turn the UPS and transformer OFF.
9
Press the UPS's OFF button until you hear a beep. Your load will still be energized.
The inverter is now off, but your UPS is not fully deactivated. The LCD Display
will show "BYPASS MODE."
Turn the UPS's Input and Output Circuit Breakers OFF. If the UPS is connected to
a transformer, turn the transformer's AC Input and Output Circuit Breakers OFF.
Your load will no longer be energized, and the LCD display will be dark.