Trimpot Setting Chart; Control Modifications; Two Speed Operation; Dynamic Braking - DART Controls 250G CONTROL Serie Manual De Instrucciones

Ocultar thumbs Ver también para 250G CONTROL Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

* These settings apply when using a 5000W Master Speedpot.
* Settings will differ when using various options, such as using the -5 or the -7 option.
For the -17B option, Accel/Decel is 20 seconds when pot is turned fully clockwise.
* This trimpot chart is approximate. Use it in conjunction with the Adjustment Procedures.
MIN MAX ACCEL I.R.
C.L.
2
5
1
G
2
5
3
G

TWO SPEED OPERATION

Two pot operation is done using two 10K
ohm speed potentiometers in parallel (both
HI's to P1-3, both LO's to P1-1). The
WIPER is switched using a SPDT switch.
TWO 10K SPEEDPOTS
P1
-1
-2
SPDT
-3

TRIMPOT SETTING CHART

H.P.
INPUT VOLTAGE
OUTPUT VOLTAGE
1/50
120VAC
0-90VDC
1/20
120VAC
0-90VDC
1/8
120VAC
0-90VDC
1/8
120VAC
0-90VDC
1/4
120VAC
0-90VDC
1/3
120VAC
0-90VDC
1/2
120VAC
0-90VDC
3/4
120VAC
0-90VDC
1.0
120VAC
0-90VDC

CONTROL MODIFICATIONS

LO
LO
W
W
HI
HI
HI
MIN MAX ACCEL I.R.
2
5
3
G

DYNAMIC BRAKING

A DPDT switch is used to inhibit the control and to connect the
DBR. Typical values for the DBR (dynamic brake resistor) are 5
ohms for 120V, 10 ohms for 240V (both 35W to 50W). Note that
motor horsepower, inertia, and cycle time effect sizing of the DBR.
NOTE: This modification cannot be used with the -17B option.
P1
LO
-1
-2
W
-3
HI
-4
-5
7
C.L.
H.P.
INPUT VOLTAGE
OUTPUT VOLTAGE
1/4
240VAC
1/2
240VAC
3/4
240VAC
1.0
240VAC
1.5
240VAC
2.0
240VAC
P2
INHIBIT
DPDT SWITCH (N.C.)
DYNAMIC
MOTOR
BRAKE
RESISTOR
0-180VDC
0-180VDC
0-180VDC
0-180VDC
0-180VDC
0-180VDC