Installation; Selecting The Installation Site - Thermor AEROMAX SPLIT 2 Manual De Instalación

Ocultar thumbs Ver también para AEROMAX SPLIT 2:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 59
Warnings
1.

Installation

1.1.

Selecting the installation site

Install the water heater in a frost-protected room.
Position it as close as possible to the main loads.
Insulate its piping if the device is installed outside of premises suitable as living
space (storage rooms, garages). The ambient temperature around the water heater
must not exceed 40 °C.
Make sure the bearing element on which the appliance is mounted can support the
weight of the appliance filled with water.
Provide 500 mm clearance in front of each electrical component to facilitate the hea-
ting element's periodic servicing.
If the appliance is set up on a false ceiling, the attic or above living space, a drain pan
is to be installed underneath the water heater. A drainage connected to the sewer
system is required.
The refrigerant line in between external aggregate and water heater must be at
least of 5 metres length and must not exceed 20 metres in length and 10 metres
in height.
Highest point in
the circuit
10 m maximum
elevation
Lowest point
in the circuit
Presentation
PLEASE NOTE : The refrigerant
line in between external aggre-
gate and water heater must not
exceed 20 meters in length and
10 meters in height
External aggregate with
Flush the refrigerant line and
an initial filling amount of
the water heater with a vacuum
0.85 kg refrigerant R410A
pump before putting the device
L3
L2
L4
L1
Line length = L1 + L2 + L3 + L4 + L5 ≤ 20 m
Installation example
Installation
into service
L5
11