ELECTRICAL REQUIREMENTS
Single Advantium Installation
Product rating is 120/208 or 120/240 volt, 60 Hz,
30 amps. This product must be connected to a supply
circuit of the proper voltage and frequency and protected
by a time delay fuse or circuit breaker. Power should be
supplied from a separate, dedicated 30-ampere branch
circuit. Wire size must conform to the requirements of the
National Electrical Code or the prevailing local code.
Combined Advantium and Wall Oven Installation
When installed in combination with a single wall oven, use
separate electrical junction boxes.
Refer to single oven installation instructions for electrical
requirements of that product.
These connections must be made by a qualified
electrician. All electrical connections must meet National
Electrical Code or prevailing local codes.
Combined Advantium and Warming Drawer
Installation
When installing the Advantium oven over an electric
warming drawer, a separate 120V, 60Hz, properly
GROUNDING INSTRUCTIONS
WARNING
Improper use of the grounding plug can result in a risk of electric shock.
This appliance must be connected to a grounded, metallic, permanent wiring system, or an equipment
grounding conductor should be run with the circuit conductors and connected to the equipment grounding
terminal or lead on the appliance.
INSTALL JUNCTION BOX
The conduit is located at the top right on the back of the
oven.
Locate and install the junction box within reach of the
oven conduit.
• Through the left or right sides of the cabinet wall
and into adjacent cabinet.
• Or, through the cutout floor.
• Or, in the upper cabinet.
4
Installation Preparation
grounded receptacle must be installed. See instructions
packed with the warming drawer.
WARNING
• The electrical power to the oven branch circuit must
be shut off while line connections are being made.
• Use copper wiring only.
• Electrical ground is required on this appliance. The
free end of the green wire (ground wire) must be
connected to a suitable ground. This wire must remain
grounded to the oven.
• If cold water pipe is interrupted by plastic,
non-metallic gaskets, union connections or other
insulating materials, DO NOT use for grounding.
• DO NOT ground to a gas pipe.
• DO NOT have a fuse in the NEUTRAL or
GROUNDING circuit. A fuse in the NEUTRAL or
GROUNDING circuit could result in an electrical shock.
• Check with a qualified electrician if you are in doubt
as to whether the appliance is properly grounded.
Failure to follow these instructions could result in
serious injury or death.
Cutout
Height
31-2000356 Rev. 0