check before each start-up
START-UP FROM "LOCAL/START" FRONT
PANEL
1. Position the LOCAL START / REMOTE
START (I6) selector on LOCAL START;
2. make sure the load plugs are disconnected
or the G.F.I. switch (D) is not inserted
(intervention/insertion lever facing
down), so as to ensure the motor's
start-up without any loads inserted;
3. open the gasoline tap (87) by turning it
towards the inside;
OFF
ON
START
4.
turn the start-up key (Q1) to the
ON position;
5. press the CHOKE button (L6) and
simultaneously turn the key to the START
position, holding it until the motor has started;
6. leave the key in the ON position, then wait a
few moments before releasing the choke
button; if the motor tends to shut itself off
press the choke button once again until the
motor has properly started up.
☞ Do not use the CHOKE button if the motor
is hot or if the ambient temperature is
sufficiently high.
Start-up
☞ ☞ ☞ ☞ ☞ In case of unsuccessful start-up, do
not insist for longer than 5 seconds.
Wait 10 seconds before attempting
another start-up .
REMOTE START
The unit can also be started by means of the
remote TCM 5 control device, or through the
EAS 5 automatic intervention panel.
1. Position the LOCAL START / REMOTE
START (I6) selector on REMOTE START;
2. Connect to the EAS (B3) connector the TCM
5 or the EAS 5 panel.
Start-up with TCM 5
Use the controls located on the TCM 5 in the
same manner as described for start-up from
the front panel.
Start-up with EAS 5
The EAS 5 panel will automatically manage
the start-up.
See operating manual for EAS 5 panel.
CAUTION
RUNNING-IN
During the first 50 hours of operation, do not use more
than 60% of the maximum output power of the unit and
check the oil level frequently, in any case please stick
to the rules given in the engine use manual.