DOMIproject F 24 D
Accessing the electrical terminal block
Follow the instructions given in fig. 8 to access the electrical connection terminal board.
The layout of the terminals for the various connections is also given in the wiring diagram
in fig. 21.
72
139
fig. 8 - Accessing the terminal block
3.6 Fume ducts
Important
The unit is a "C type" with sealed chamber and forced draught, the air inlet and fume out-
let must be connected to one of the following extraction/suction systems. The unit is ap-
proved for operation with all the Cny flue configurations given on the dataplate. Some
configurations may be expressly limited or not permitted by law, standards or local reg-
ulations. Before installation, check and carefully follow the instructions. Also, comply with
the instructions on the positioning of wall and/or roof terminals and the minimum distanc-
es from windows, walls, ventilation openings, etc.
Baffles
Boiler operation requires fitting the baffles supplied with the unit. Check that the boiler
has right baffle (if to be used) and its correct positioning.
A
B
3
1
2
2
1
A Baffle replacement with boiler not installed
B Baffle replacement with boiler and fume ducts already installed
Connection with coaxial pipes
fig. 9 - Examples of connection with coaxial pipes (
Table. 2 - Typology
Type
Description
C1X
Wall horizontal exhaust and inlet
C3X
Roof vertical exhaust and inlet
138
3
5
6
4
= Air /
= Fumes)
cod. 3540V402 - Rev. 00 - 9
For coaxial connection, fit the unit with one of the following starting accessories. For the
wall hole dimensions, refer to the figure on the cover.
100
60
010006X0
010018X0
fig. 10 - Starting accessory for coaxial ducts
Table. 3 - Baffles for coaxial ducts
Max. permissible length
Reduction factor 90° bend
Reduction factor 45° bend
0 ÷ 2 m
Baffle to use
2 ÷ 5 m
Connection with separate pipes
C
5x
fig. 11 - Examples of connection with separate pipes (
Table. 4 - Typology
Type
Description
C1X
Wall horizontal exhaust and intake. The inlet/outlet terminals must be concentric or close enough to be
undergo similar wind conditions (within 50 cm)
C3X
Roof vertical exhaust and intake. Inlet/outlet terminals like for C12
C5X
Wall or roof exhaust and intake separate or in any case in areas with different pressures. The exhaust
and intake must not be positioned on opposite walls.
C6X
Intake and exhaust with separately certified pipes (EN 1856/1)
B2X
Intake from installation room and wall or roof exhaust
IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
For the connection of separate ducts, fit the unit with the following starting accessory:
80
fig. 12 - Starting accessory for separate ducts
Before installation, check the baffle to be used and make sure the maximum permissible
length has not been exceeded, by means of a simple calculation:
1.
Establish the layout of the system of split flues, including accessories and outlet ter-
minals.
2.
Consult the table 6 and identify the losses in m
ponent, according to the installation position.
3.
Check that the sum total of losses is less than or equal to the maximum permissible
length in table 5.
Ø126
Ø82
Ø60
Ø130
010007X0
Coaxial 60/100
Coaxial 80/125
5 m
10 m
1 m
0.5 m
0.5 m
0.25 m
Ø 43
0 ÷ 3 m
no baffle
3 ÷ 10 m
B
C
2x
1x
= Air /
80
010011X0
(equivalent metres) of every com-
eq
EN
Ø 43
no baffle
= Fumes)
27