Ubicación de las Etiquetas de Seguridad
Información para volver a pedir Etiquetas de Seguridad
Ubicación
Mensaje de Seguridad Alerta
A
PELIGRO
B
ADVERTENCIA
C
ADVERTENCIA
D
ADVERTENCIA
E
ADVERTENCIA
▲ Esta parte es un marbete que se debe quitar y eliminar después de que el interruptor haya sido instalado y ajustado .
INSTALLATION OF PIERCING SET SCREWS
(See illustrations on reverse side of tag)
1. Be sure that cutting tip of piercing set screw does not protrude through
the coupling body before installing operating pipe.
2. Install operating pipe section in coupling and finger tighten clamp bolt.
See Figure 1.
3. Adjust operating pipe. Then tighten clamp bolt.
4. Tighten piercing set screw, piercing the pipe, and continue turning until
firm resistance is felt. See Figure 2.
5. Make sure clamp bolt is tight.
Failure to properly install piercing set screws can cause slippage of
A
operating pipe, causing improper operation of switch, arcing, damage,
or electrical shock.
D
D
Riesgo de Electrocución
Tornillos Perforantes de Sujeción
Operación con Palanca
Riesgo de Electrocución—Banda de Conexión a Tierra
Ajuste del Mecanismo de Operación