6. Operation Principles

6.2.7 Shutdown Mode

When the UPS is in the off state and utility power source is absent, the UPS will enter Shutdown Mode. When the utility power source
is absent and the UPS has discharged the batteries to the cut-off voltage level of 10V/battery at 25C, the UPS will also enter into a
Shutdown Mode. When the UPS enters this mode, it will shut off the control power of the UPS and rectifier, and shut down the charger
and inverter.
Q4
Maintenance Breaker
STS
Single
Input
Rectifier
Inverter
Main
Load
Q1
Inverter
Q3
Input Breaker
Relay
Output Breaker
Battery Breaker
Q4
Maintenance Breaker
STS
Bypass
Q2
Dual
Bypass Breaker
Inverter
Rectifier
Inputs
Main
Load
Q1
Inverter
Q3
Input Breaker
Relay
Output Breaker
Battery Breaker
Shutdown Mode Diagrams