7. UPS Operation

7.3.2 Transfer Critical Load from Maintenance Bypass to Line Mode

Turn ON the battery breaker (external battery cabinet).
Step 1
Step 2
Single input model:
Turn ON the Q1 Input 1 breaker.
S3M100KX/S3M120KX
(100 kVA/200 kVA) Models
Dual input model (Option):
Turn ON the Q1 Input breaker and Q2 Input breaker.
S3M100KX/S3M120KX
(100 kVA/200 kVA) Models
Go to the LCD INFORMATION Menu. Choose "SYSTEM" to ensure that Bypass Mode is enabled ("Power By Bypass"). If
Step 3
Bypass Mode is disabled, set it to "enabled" through the SETUP menu and confirm the UPS is operating in Bypass Mode
before proceeding.
Step 4
Proceed to Step 5.
Q1
Input 1
Q1
Q2
Input 1
Input 2
00KVA/120KVA
Single input model:
Turn ON the Q1 Input 1 breaker.
S3M160KX/S3M200KX
(160 kVA/200 kVA) Models
Dual input model (Option):
Turn ON the Q1 Input breaker and Q2 Input breaker
Q1
Input 1
S3M160KX/S3M200KX
(160 kVA/200 kVA) Models
160KVA/200KVA
Turn ON the Q3 Output breaker.
S3M160KX/S3M200KX
(160 kVA/200 kVA) Models
59
Q1
Input 1
Q2
Input 2
2018/01/01
Q3
Output