6 – Standard Operation

6-4 Battery Mode Startup (Cold Start)

The UPS system supports battery mode startup (cold start), allowing it to operate as a standalone power source when AC input power is
unavailable.
1.
Make sure the UPS system is properly installed and the battery is at least partially charged.
2.
Some electronic equipment may draw more amps during startup; consider reducing the initial load on the UPS system.
3.
Press the ON button
for approximately 5 seconds, then release it. The UPS will beep twice and the LCD screen will change from
4.
Press the ON button
again for approximately 3 seconds, then release it. The UPS will beep twice and the LCD screen will change from
to
. (The UPS system will remain awake for approximately 15 seconds after completing the previous step. If you do not press the ON
G
H
button again before 15 seconds have elapsed, you will need to repeat the previous step.)
5.
The UPS system will run a self-test and display
battery is depleted (or until pre-defined shutdown parameters have been reached).
G
This screen indicates the UPS inverter is off and utility input is abnormal.

6-5 UPS System Shutdown

1.
Press the OFF button for approximately 5 seconds, then release it. The inverter output will turn off and the LCD screen will show
2.
Turn off the UPS system's utility input breaker.
3.
The UPS system is now completely off. If the UPS system will be turned off for a significant length of time, follow the battery recharging
instructions in Section 11 – Storage and Service.
B
This screen indicates the UPS inverter is off.

6-6 UPS System Settings and Measurements

Checking UPS System Measurements
To check the values measured by the UPS, scroll up
order:
I
Bypass Input Voltage
J
Utility Input Frequency
K
Bypass Input Frequency
continued
again. Battery mode startup is successful and connected equipment will operate until the
H
or down
through the LCD panel. Scrolling down will display values in the following
L
Output Voltage
M
Output Frequency
N
Output Load Percentage
13
H
This screen shows the utility input voltage is zero.
O
Battery Voltage
P
Inner Temperature (°C)
to
.
A
G
.
B