Parámetros: 9-** Profibus - Danfoss FC 300 Guía De Programación

Ocultar thumbs Ver también para FC 300:
Tabla de contenido
Descripciones de parámetros
3.11 Parámetros: 9-** Profibus
9-00 Setpoint
Range:
Función:
0
[0 -
Este parámetro recibe referencia cíclica de un
*
65535 ]
maestro clase 2. Si la prioridad de control está
establecida para Master Class 2, la referencia
para el convertidor de frecuencia se toma de
este parámetro, mientras la referencia cíclica se
ignora.
9-07 Actual Value
Range:
Función:
0
[0 - 65535 ] Este parámetro proporciona el MAV para un
*
Master Class 2. El parámetro es válido si la
prioridad de control está establecida a Master
Class 2.
9-15 PCD Write Configuration
Indexado [10]
Option:
[0]
None
*
[302]
Minimum Reference
[303]
Maximum Reference
[312]
Catch up/slow Down Value
[341]
Ramp 1 Ramp up Time
[342]
Ramp 1 Ramp Down Time
[351]
Ramp 2 Ramp up Time
[352]
Ramp 2 Ramp down Time
[380]
Jog Ramp Time
[381]
Quick Stop Ramp Time
[411]
Motor Speed Low Limit [RPM]
[412]
Motor Speed Low Limit [Hz]
[413]
Motor Speed High Limit [RPM]
[414]
Motor Speed High Limit [Hz]
[416]
Torque Limit Motor Mode
[417]
Torque Limit Generator Mode
[590]
Digital & Relay Bus Control
[593]
Pulse Out #27 Bus Control
[595]
Pulse Out #29 Bus Control
Guía de programación del FC 300
Función:
Seleccionar los
parámetros para su
asignación a los PCD 3 a
10 de los telegramas. El
número de los PCD
disponibles depende del
tipo de telegrama. Los
valores de PCD 3 a 10 se
escribirán en los
parámetros seleccionados
como valores de datos.
Como método alternativo,
especifique un telegrama
Profibus estándar en
9-22 Telegram Selection.
®
MG33MD05 - VLT
es una marca registrada de Danfoss.
9-15 PCD Write Configuration
Indexado [10]
Option:
[597]
Pulse Out #X30/6 Bus Control
[653]
Term 42 Output Bus Ctrl
[663]
Terminal X30/8 Bus Control
[673]
Terminal X45/1 Bus Control
[683]
Terminal X45/3 Bus Control
[748]
PCD Feed Forward
[890]
Bus Jog 1 Speed
[891]
Bus Jog 2 Speed
[1680] Fieldbus CTW 1
[1682] Fieldbus REF 1
[1685] FC Port CTW 1
[1686] FC Port REF 1
[3310] Sync Factor Master
[3311] Sync Factor Slave
[3401] PCD 1 Write to MCO
[3402] PCD 2 Write to MCO
[3403] PCD 3 Write to MCO
[3404] PCD 4 Write to MCO
[3405] PCD 5 Write to MCO
[3406] PCD 6 Write to MCO
[3407] PCD 7 Write to MCO
[3408] PCD 8 Write to MCO
[3409] PCD 9 Write to MCO
[3410] PCD 10 Write to MCO
9-16 PCD Read Configuration
Indexado [10]
Option:
[0]
None
*
[15]
Readout: actual setup
[1472] Legacy Alarm Word
[1473] Legacy Warning Word
[1474] Leg. Ext. Status Word
[1500] Operating Hours
[1501] Running Hours
[1502] kWh Counter
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
Función:
Función:
Seleccionar los parámetros
para su asignación a los PCD
3 a 10 de los telegramas. El
número de PCD disponibles
depende del tipo de
telegrama. Los PCD 3 a 10
contienen los valores reales
de los parámetros
seleccionados. Para
telegramas Profibus estándar,
véase 9-22 Telegram Selection.
119
3
3