Outdoor Unit Installation Drawings
Max. allowable length
Min. allowable length
*
Max. allowable height
Additional refrigerant
required for refrigerant
pipe exceeding
10m in length.
Gas pipe
Liquid pipe
*
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced perfomance.
*
The suggested shortest pipe length is 1.5m, in order to avoid
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
In sites with poor drainage, use
block bases for outdoor unit.
Adjust foot height until the unit
is leveled. Otherwise, water
leakage or pooling of water may
occur.
■English
15m
1.5m
12m
20g/m
O.D. 9.5mm
O.D. 6.4mm
Where there is a danger of the unit
falling, use foot bolts, or wires.
unit: mm
Wrap the insulation pipe with
the finishing tape from bottom
to top.
CAUTION
Set the piping length from
1.5m to 15m.
Stop valve cover
How to remove the stop
valve cover
Remove the screw on the
stop valve cover.
Slide the lid downward
to remove it.
How to attach the stop
valve cover
Insert the upper part of
the stop valve cover into the
outdoor unit to install.
Tighten the screws.
Allow space for piping
and electrical servicing.
3