INSTALLATION
8.3

General installation diagram

WARNING:
b
Danger of breakdowns or malfunction.
Observe the minimum clearences indicated in Figure
8.1.
A
G
E
F
H
E
Fig. 8.1
General diagram of the installation and the minimum
assembly distances.
Legend
A
Clearance to ceiling above (minimum 5 cm)
B
Height in relation to the floor (minimum 2 m)
C
Rear clearance (minimum 20 cm)
D
Side clearance connections side (minimum 30 cm)
E
Front clearance (minimum 100 cm)
F
Side clearance opposite side connections (minimum 20 cm)
G
Clearance to the front of the internal unit (minimum 10 cm)
WARNING:
b
Danger of breakdowns or malfunction.
The minimum assembly distance between the indoor
and outdoor units must not be less than three meters,
otherwise there are risks of malfunction and noise from
the outdoor unit.
- 10 -
B
A
D
B
F
C
G
D
9

Installation of the indoor unit

9.1

Selecting the clearance location

WARNING:
b
Danger of breakdowns or malfunction.
Observe the minimum clearances indicated in Figure
8.1.
NOTE:
i
If a hole already exists in the wall or a refrigerant pipe
or condensed water pipe has already been installed,
the base plate can be mounted to adapt to these
conditions.
Recommendations
- Install the indoor unit close to the ceiling,ensuring minimum
clearances are met.
- Choose a position site that will allow air to reach all parts of
the room evenly. Avoid beams, obstructions or lights which
would interfere with the airflow.
- Install the indoor unit at an adequate distance from chairs or
workstations in order to avoid unpleasant draughts.
- Avoid installing close heat sources.
9.2

Fixing the mounting plate

Carry out the steps described below:
• Place the mounting plate on the chosen installation point.
• Level the plate horizontally and mark the position of holes to
be made on the wall.
• Remove the plate.
WARNING! Danger of breaks in the domestic
b
installation:
Check that there are no electricity cables, pipes or
any other services which could be damaged when the
mounting holes are drilled. If other services are found,
choose another installation location and repeat the
aforementioned steps.
• Make the holes using a drill and insert the rawl plugs.
• Place the mounting plate in position, level it horizontally and
fix it with the screws and the plugs.
WARNING:
b
Danger of breakdowns or malfunction.
Ensure that the mounting plate has been correctly
levelled. Otherwise, disassemble the plate and
assemble it again correctly. Failure to do so could lead
to water leaks.