G-U BKS B-1893 Serie Manual De Instalación página 63

Cerradura con pestillo motorizada para sistemas de marcos tubulares
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

7.
Troubleshooting
Problem
Lock does not unlock
Locks unlocks
automatically
Red LED flashes
Controller beeps
Cause
y
y
Missing or faulty power
supply
(measure 24 V; terminal
G2 and V2)
y
y
No + 24 V control signal
y
y
Emergency power backup
system B-54903-23-3-9 is
not connected and jumper is
inserted
y
y
Mechanically blocked
- Door leaf or door frame is
twisted or warped
- Active leaf is jammed
- Screws are pressing
against the lock case or
vertical rods
y
y
The control unit is in
programming mode
y
y
Test run not completed
successfully
y
y
Deadbolt of the active leaf
lock (only B-1893x) has
been moved to the locked
position
y
y
Continuous signal at control
input
y
y
Incorrect cable assignment
y
y
Controller defective
y
y
Error source according to
blink code
y
y
Error source according to
beep codes
Help
y
y
The controller must be
supplied with at least
21 V DC
y
y
Check that the power supply
unit, fuse and cable cross-
sections are sufficiently
sized and replace if
necessary
y
y
Check control input I1/I2
y
y
Remove the jumper or
connect emergency
power backup system
B-54903-23-3-9
y
y
Remove blockage
- Check door leaf/frame
- Check active-leaf lock
- Check screws and shorten
if necessary
y
y
Exit or abort programming
mode (see point 6.2)
y
y
Perform test run
(see point 6.5)
y
y
Unlock the active leaf
y
y
Check wiring (see point  2.4)
y
y
Check control signal
(terminal I1 and I2)
y
y
Check cable assignment
between lock and controller
(see point 2.4)
y
y
Replace controller
y
y
See point 5.1
y
y
See point 5.2
63
Tabla de contenido
loading

Este manual también es adecuado para:

Bks b-1993 serie

Tabla de contenido