Performing A Test Run - G-U BKS B-1893 Serie Manual De Instalación

Cerradura con pestillo motorizada para sistemas de marcos tubulares
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Installation instructions
B-1893x | B-1993x
Motor-driven shoot-bolt lock for narrow stile systems
ATTENTION
62
6.5

Performing a test run

When making changes to or replacing individual components (controller B-54900-01-3-9, motor-
driven shoot-bolt lock B-1893x/B-1993x or connection cable B 5490 0300) you must perform a
test run!
Open the door and make sure it cannot be closed accidentally.
Then put the controller into programming mode. Any existing blink codes must be acknowledged
(see 6.3) before a test run can be carried out.
Send a control signal on control input I2 to trigger the test run. The motor-driven shoot-bolt lock
performs a complete travel cycle at slow speed.
If no errors occur during the test run, the red LED at the controller B-54900-01-3-9 lights up. The
signal contact 1 "Locked by motor" closes.
If an error occurs, the controller outputs corresponding blink codes (see 5.1).
You can operate the door by removing the service plug to exit the programming mode.
EN
10.2017 | 20734ES | Designed in Germany
Tabla de contenido
loading

Este manual también es adecuado para:

Bks b-1993 serie

Tabla de contenido