Lamborghini Caloreclima ECO 14/2 Manual Para La Instalación Y El Mantenimiento página 22

Quemadores para gasóleo
Ocultar thumbs Ver también para ECO 14/2:
Tabla de contenido
If the burner is locked out, there will be a steady red light on the lock out pushbutton.
By pressing the transparent pushbutton, the control and checking device will be released.
By pressing it for more than 3 seconds, the diagnosis stage will be activated (red light flashes rapidly). The
table below describes the causes of the lock out or fault in relation to the number of flashes (always red).
The diagnosis function is interrupted by pressing the release button for at least 3 seconds.
Visual indication
2 flashes
4 4
3 flashes
4 4 4
4 flashes
4 4 4 4
5 flashes
4 4 4 4 4
6 flashes
4 4 4 4 4 4
7 flashes
4 4 4 4 4 4 4
8 flashes
4 4 4 4 4 4 4 4
9 flashes
4 4 4 4 4 4 4 4 4
10 flashes
4 4 4 4 4 4 4 4 4 4
DIAGNOSIS OF LMO EQUIPMENT FAULTS AND LOCK OUT
Description of operating anomalies
Possible causes
No flame signal
Faulty fuel valves
-
Faulty flame detector
-
Incorrect burner setting, no fuel
-
No ignition
-
Not used
Stray light on ignition
Not used
Not used
No flame signal during operation
Faulty fuel valves
-
Faulty flame detector
-
Incorrect burner setting, no fuel
-
Anomalies in fuel preheating time
Not used
Incorrect electrical connection or damage to equipment
22
Tabla de contenido
loading

Este manual también es adecuado para:

Eco 22/2

Tabla de contenido