16 00
Safety margin for timed operation to allow for inertia
00
3 seconds
01
6 seconds (useful for hydraulic motors, which have greater inertia)
For timed operation: when programming the operating time, it is best to always set a safety margin (3-4
seconds) to ensure that the gate always completes its cycle, even with different weather conditions (wind,
low temperatures). When movement is reversed - such as when photocells are triggered - motors are made
to run in the reverse direction for the exact same time that they had run before, plus a safety margin (to
allow for inertia).
When dealing with hydraulic motors, which have greater inertia, you have the option of increasing this
margin - to make extra sure that the gate will complete its cycle - from the default setting of 3 seconds to
the higher value of 6 seconds.
The parameter is only visible if the encoder is disabled (
21 30
Auto-closing pause time
00
90
SECONDS
-
92
99
from 2 to 9 MINUTES
-
2-
NOTE: parameter
When one of the photocells' beams is broken, the timer is reset and the countdown is restarted once the
photocell is clear.
22 20
Motor 1 operating time
23 20
Motor 2 operating time
00
99
SECONDS of operation
-
The parameter is only visible if the encoder is disabled (
24 00
Double operating time
00
OFF (normal operating time)
01
ON (operating time is doubled)
Used for installations with particularly long operating times.
The parameter is only visible if the encoder is disabled (
25 03
Opening time lag (for motor 2)
00
10
SECONDS
-
26 05
Closing time lag (for motor 1)
00
60
SECONDS
-
4-
NOTE: parameter
27 02
Reverse time after safety edge or anti-crush device is triggered
00
60
SECONDS
-
Determines how long, in seconds, the gate reverses for after meeting an obstacle; if set to a value high
enough for the gate to open fully, the gate will also auto-close according to the rules established by
49
parameter
.
36
in easy setup mode.
in easy setup mode.
75 00
).
75 00
).
75 00
).