When flushing phase is completed, the system and or components are
full of liquid refrigerant. The canister contains the contaminated refrigerant.
You need now to prepare the recovery phase...
The Display shows:
O p e n
o n l y
C l o s e
H P
E N T E R
t o
Press Enter to confirm.
Now the refrigerant recovery is starting in order to empty the system
and the flushing canister. This process can last several minutes.
The Display shows:
F l u s h i n g
P r e s s u r e
Q u a n t i t y
■ ■ ■ ■ ■ ■ ■ ■ ■ ■
When recovery is completed, the unit performs a pressure test, in order
to verify if there is residual refrigerant trapped in the system and / or
the canister due to icing. Any sudden pressure increase will re-activate
the recovery, until system is considerate as perfectly empty.
The Display shows:
F l u s h i n g
P r e s s u r e
t e s t .
After the pressure test, the Konfort unit is draining the liquid contamination
Into to "used oil" bottle. (Compressor oil, UV additive)
The Display shows:
D r a i n e d
T i m e
Q u a n t i t y
After the count down draining of liquid contamination is completed and
quantity is indicated in cc. (No indication of quantity with
Konfort ECK605E, 610E & 610E BUS)
The display shows:
ACKF01_GB_00
L P
v a l v e
v a l v e
c o n f i r m .
m B . x x x x x
g . x x x x x
i n c r e a s e
m B . - x x x
S e c . x x x x
o i l
c h e c k .
S e c .
c c . x x x