When the vacuum phase is completed, the unit performs a
connection leak test:
The Display shows:
F l u s h i n g
L e a k
t e s t .
Default leak check time is 240 seconds, but it can be shorted by
pressing UP or DOWN. You can also cancel and completely quit
the program by pressing the Stop button.
LEAKAGE WARNING!
If a leak is detected the following message appears with also the
current vacuum value. Verify connection to system and/or components.
L e a k a g e !
E N T E R
t o
Press Stop to cancel and quit the program for fixing a major problem
(Important leak). Or press Enter to continue if you could solve
immediately the issue. (Tightness of one connection).
If no leakage has been detected, the system is ready for flushing.
The Display shows:
O p e n
o n l y
C l o s e
L P
E N T E R
t o
Press Enter to confirm.
Now the refrigerant flushing phase is starting.
The refrigerant flows into the system, and arrives inside the flushing canister.
The Display shows:
F l u s h i n g
A / C
s y s t e m
F i l l i n g
Q u a n t i t y
ACKF01_GB_00
S e c . x x x x
m B . x x x x
c o n t i n u e
m B . x x x x
H P
v a l v e
v a l v e
c o n f i r m .
p h a s e
g . x x x x x