menús de selección - regulación - diagnóstico
description
4 ZONE 1 PARAMETER
4 0 ZONE 1 TEMPERATURE SETTING
4 0 0 Zone 1 comfort temperature setting
4 0 1 Zone 1 reduced temperature setting
4 0 2 Heating fi xed temperature setting
4 1 Entering access code
4 2 ZONE 1 SETTING
4 2 0 Heating appliance temperature value
setting
4 2 1 Basic heating control type selection
type depending on the peripheral
devices connected
4 2 2 Slope
If the external sensor is used, the boiler
calculates the most suitable heating
fl ow temperature taking the external
temperature and the type of appliance
into account.
The type of curve must be chosen
according to the type of appliance
radiator and the heat losses present in
the building.
4 2 3 Parallel shift
To adapt the thermal curve to the appliance requirements, it is possible to perform a parallel shift of the curve in order to alter
the calculated fl ow temperature and therefore the ambient temperature.
The shift value between - 20 and + 20 is shown on the display. Each level corresponds to a 1°C increase in the fl ow temperature
in relation to the initial setting.
4 2 4 Compensation
4 2 5 Zone 1 heating maximum temperature
setting
4 2 6 Zone 1 heating minimum temperature
setting
4 3 DIAGNOSTICS
4 3 0 Zone 1 room temperature
4 3 1 Zone 1 set temperature
4 3 2 Zone 1 heat request
4 3 3 Pump status
4 4 ZONE DEVICE MANAGEMENT
4 4 0 Pump control
settings - adjustment - problem identifi cation menus
value
from 10 to 30 °C
from 10 to 30 °C
from 20 to 82 °C
0 = from 20 to 45°C (low temp.)
1 = from 35 to 85°C (high temp.)
0 = fi xed fl ow temperature
1 = device On/Off
2 = ambient sensor only
3 = external sensor only
4 = ambient sensor +
external sensor
0_2 to 3_5
°C
100
90
80
70
60
50
40
30
- 20 to + 20
0 to + 20
if setting = 0, the temperature taken from the ambient sensor does not aff ect the
calculation of the setting.
If setting = 20, the temperature taken has maximum infl uence on the setting.
35 to + 82°C
20 to + 45°C
35 to + 82°C
20 to + 45°C
0=OFF
1=ON
0=OFF
1=ON
0=OFF
1=ON
19
Activated only with the modulating device
connected (option)
16
70
Activated only with temperature control and
fi xed temperature
222 turn the encoder clockwise to select 234 and
press the M
/O
button
ENU
K
1
select in the appliance type base
1
To activate heating control, press the AUTO
button. The display lights up the AUTO symbol,
indicating the peripheral device connected (if
present)
1_5
3.5
3.0
2.5
2.0
10
5
0
-5
-10
-15
External temperature
temperatura esterna
0
20
82
if parameter 420 = 1
45
if parameter 420 = 0
35
if parameter 420 = 1
20
if parameter 420 = 0
display only
Activated only with the modulating device
connected (option)
Only active with Heating Zones Modules
Management
Only active with Heating Zones Modules
Management
1.5
1.2
1.0
0.8
0.6
0.4
0.2
-20 °C
41