menús de selección - regulación - diagnóstico
description
2 4 BOILER PARAMETER - PART 2
2 4 0
NOT PRESENT
2 4 1
NOT PRESENT
2 4 2
NOT PRESENT
2 4 3 Post-ventilation after heating request
2 4 4 Time delay after heating temperature
increase
This parameter allows the time delay to be set before automatic increase of the fl ow temperature calculated in increments of
4°C (max 12°C). If this parameter retains the value 00, this function is not active.
2 4 5 NOT PRESENT
2 4 6 NOT PRESENT
2 4 7 Device indicator for heating circuit
pressure
2 4 8 NOT PRESENT
2 5 DOMESTIC HOT WATER PARAMETER
2 5 0
NOT PRESENT
2 5 1
NOT PRESENT
2 5 2
NOT PRESENT
2 5 3
NOT PRESENT
2 5 4 Post-circulation and post-ventilation
after a domestic hot water draw-off
2 5 5 Domestic hot water timer
2 9 RESET MENU 2
2 9 0 Automatically resetting to the default
setting in menu 2
3 BOILER WITH TANK (INTERNAL OR EXTERNAL) AND SOLAR APPLIANCE CONNECTION
3 0 GENERAL SETTING
3 0 0
Storage Setpoint Temperature
3 0 1
NOT PRESENT
3 0 2
NOT PRESENT
3 1 Entering access code
3 2 SPECIAL SETTING
3 2 0 Anti-legionella function
This function prevents the formation of Legionnaire's disease bacteria which may develop in the piping and indirect
cylinders at temperatures between 20°C and 40°C. If activated, whenever the indirect cylinder temperature stays below
59°C for over 100 hours, the boiler heats the water in the indirect cylinder until it reaches 65°C for 30 minutes.
3 2 1
NOT PRESENT
3 2 2
NOT PRESENT
3 2 3 Collector delta temp pump ON
3 2 4 Collector delta temp pump OFF
3 2 5 Minimum collector temp pump ON
2 2 6 Collector kick
3 2 7 Recooling function
3 2 8
NOT PRESENT
3 2 9 Collector frost protection temperature
settings - adjustment - problem identifi cation menus
value
0 = OFF
1 = ON
from 0 to 60 minutes
0 =
temperature sensor
only
1 = pressure switch at
minimum
2 = pressure sensor
0 = OFF
1 = ON
OFF = 3 minutes post-circulation and post-ventilation after domestic hot water
draw-off if the boiler temperature measured requires it.
ON = always on for 3 minutes post-circulation and post-ventilation after domestic
hot water draw-off .
from 0 to 60 minutes
Reset
OK = yes
ESC = no
from 40 to 60°C
0 = OFF - 1 = ON
from 0 to 30°C
from 0 to 30°C
from 10 to 90°C
ON or OFF
ON or OFF
from -20 to +5°C
0
16
activated only with thermostat On/Off and
heating control activated (parameter 421 or
521 = 01
1
RESERVED FOR TECHNICAL ASSISTANCE Only
if the PCB is changed
0
0
To reset all default parameter settings, press
the MENU button
222 Turn the encoder clockwise to select 234 and
press the M
button
ENU
0
Active with the Ariston Kit connected
8
2
Enable only with Clip-In solar connected
30
(option)
OFF
OFF
-20
39