Switch Function 3, Two-Point; Switch Function 4, Duration/Inverse; Switch Function 5, Range Lv1-Lv2; Measuring Points - Heyl Testomat 2000 PO4 Manual De Instrucciones

Fotómetro de procesos para fosfato 0 –10 mg/l
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

>FUNCTION LV1
▼▲ ME
DURATION
*
Duration/inverse
Impulse
Interval
Two point
Range LV1-LV2
Time:
00m:10s
>FUNCTION LV2
▼▲ ME
DURATION
*
Duration/inverse
Impulse
Interval
Time:
00m:10s
>MEASURING POINTS ▼▲ ME
1 Measuring Point
2 Meas. Points int.
2 MEAS. POINTS EXT.
*

Switch function 3, two-point

If the upper limit value LV1 has been exceeded, the output relay LV1
switches. If the value falls below the lower limit value LV2, the output
relay LV1 drops out again. The output relay LV2 switches according
to the programmed switch function.
The function 3 is only possible if different values are used for the limit
values LV1 and LV2 with just one measuring point. For example, for
LV1 = 2 mg/l and for LV2 = 1 mg/l.

Switch function 4, Duration/inverse

If the measured value falls below the limit value LV1 or LV2, the
output relay LV1 or LV2 reacts. If the limit value LV1 or LV2 has been
exceeded, the relevant relay drops out again.
 In
, select
>BASIC PROGRAM
=>
=>
PROGRAM VALUES
 Select the duration, impulse, interval or two-point (only for LV1)
 Enter the time (only for switch function 1 and 2)
 Press "ENTER" to confirm the entry

Switch function 5, range LV1-LV2

Monitoring the range between limit values LV1 and LV2. If limit value
LV1 is exceeded, relay LV1 switches and LED "LV1" illuminates red.
If limit value LV2 is not achieved, relay LV2 switches and LED "LV2"
lights up red. If the measured value is within the range, both relays
are deactivated and both LEDs illuminate green.
If this function has been selected, the setting in the menu item
is ineffective.
FUNCTION LV2

Measuring points

®
The Testomat 2000
PO4 can be used for monitoring 2 measuring
points. Measuring point switch-over can occur either automatically or
by triggering a contact (or normally closed) at input IN1. If the
external measuring point switch-over has been programmed ("
measuring points externally
has to be connected to IN1 (volt-free contact required!). The active
status of IN1 has to be programmed accordingly.
Entering further basic program data
FUNCTION LV1 or FUNCTION LV2
"), a respective controller (e.g. timer)
2
31