>INTERFACES
▼▲ ME
Type 0-20mA
Type 4-20mA
TYPE RS232
*
Type Data Logger
>INTERFACES
▼▲ ME
Type 0-20mA
Type 4-20mA
Type RS232
TYPE DATA LOGGER
*
Flush valve
terminals 1, 2
Limit value 1
terminals 3, 4, 5
40
In
>BASIC PROGRAM
, select
=>
=>
PROGRAM VALUES
Select the desired interface
Press "ENTER" to confirm the selection
SD card data logger
With the SD card data logger (article number 100490), the
measurements of the Testomat 2000
To operate the data logger, please proceed as follows:
In
, select
>BASIC PROGRAM
=>
PROGRAM VALUES
=>
Select
TYPE DATA LOGGER
Press "ENTER" to confirm the selection
Description of the relay outputs
All relay outputs are neutral contacts. This ensures that all connection
options are available. The switching of mains voltage and external
voltage, and the direct switching of inputs, e.g. a process controller,
can be realised.
Flushing (external flush valve)
Immediately before each analysis the external flush valve is opened
for the programmed period allowing the line up to Testomat 2000
PO4 to fill with measuring water. Please ensure that the programmed
flush time is sufficient.
Please refer to "Entering further basic program data" "External
flush" for programming details
LV1 and LV2 limit value outputs
Two volt-free relay contacts are available to signal that a limit value
has been exceeded. The limit values, the hysteresis and the function
can be freely programmed for both contacts.
Function
LV1
Relay switches when the
limit value is exceeded at:
Limit value 1 or
measuring point 1
Description of the relay outputs
INTERFACES
®
can be logged continuously.
INTERFACES
Contact
Action
Volt-free
Programmable:
change-
- Continuous contact
over
- Impulse (1-99 seconds/minutes)
- Interval (1-99 seconds/minutes)
contact
- Two-step controller (only for one
measuring point)
- Hysteresis (limit value is exceeded
once, twice, three times)
®