BTL5-A/C/E/G1_-M_ _ _ _-B/Z-NEX-S32/KA_ _
Micropulse Linear Transducer - Rod Style
3
Installation (cont.)
3.3
Magnets, Installation
A magnet is required for each trans-
ducer. This must be ordered sepa-
rately. ➥ ➥ ➥ ➥ ➥ Fig. 3-4.
For mounting the magnet we rec-
ommend to use non-magnetizable
material. ➥ ➥ ➥ ➥ ➥ Fig. 3-1.
BTL-P-1013-4R
BTL-P-1013-4S
BTL-P-1012-4R
Fig. 3-4: Magnet (optional)
4
Wiring
Note the following when mak-
ing electrical connections:
System and control cabi-
net must be at the same
ground potential.
The transducer does not
have a ground terminal.
Potential compensation
must be ensured by means of a
metallic conducting installation
space.
The connecting cable
must be routed stationary
and with strain relief.
The operator must em-
ploy suitable means to
ensure that the rated volt-
age of DC 28 V is not exceeded.
To ensure the electromagnetic
compatibility (EMC) which Balluff
warrants with the CE Mark, the
following instructions must be
strictly followed.
not used
0 V
10...0 V
0...10 V
GND
+24 V
BTL5-A11-
...KA_ _
Bild 4-1: BTL5-A11...KA_ _ with controller, wiring example
Ignition Class "n"
BTL transducer and the control
must be connected using
shielded cable.
Shielding: Copper filament
braided, 85% coverage.
The shield must be tied to the
connector housing in the BKS
connector ( ➥ ➥ ➥ ➥ ➥ Fig. 4-3); see in-
structions accompanying the
connector.
In the cable version the cable
shield is connected to the hous-
ing in the PG fitting.
The cable shield must be grounded
on the control side, i.e., connected
to the protection ground.
Pin assignments can be found in
➥ ➥ ➥ ➥ ➥ Table 4-1. Connections on the
controller side may vary accord-
ing to the controller and configu-
ration used.
YE
GY
PK
GN
BU
BN
Controller with
analog input
english
5