Other Displays On The Keypad; Table 4.3 - Other Displays On The Keypad - Reliance electric SP120 Manual De Instrucciones Y Operación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

English
Problem
The speed of the motor
does not match the
frequency.
The parameters stored do
not match the values
entered.
No entries can be made.
The electronic motor
protection (fault E05) is
triggered.

4.4 Other Displays on the Keypad

Display
A reset signal has been issued.
The SP120 drive is in standby mode.
Note: If motor was running when the 18{RS} input was received, the motor will coast to a
stop.
The input voltage has been switched off.
- - -
The waiting time before automatic restart has expired (see b01 [
b03 [
The factory setting has been selected and the drive is in the initialization phase
(see b84 [
parameters for the 50 Hz version are loaded. If your drive is a U version, parameters for
the 60 Hz version are loaded.
No data present or the function is not active.
_ _ _
4-4
Table 4.2 – Drive Problems
1. Check to see that the maximum frequency has been entered correctly.
2. Check the rated speed of the motor and the reduction ratio of the gear.
3. Check to see if manual boost and current limit are set properly.
4. If PID control is used, check gain adjustments.
When the input voltage was switched off the entered values were transferred to
the power-failure safe EEPROM. Power-off time must be at least 6 sec.
Check to see if the parameter protection is activated via a digital input setting of
15 {SFT}.
1. Check the manual boost setting to see if it is too high.
2. Check the electronic motor protection setting to make sure that it is correct.
Table 4.3 – Other Displays on the Keypad
]).
RESTART TIME
] , b85 [
RESET FUNCTIONS
Corrective Action
Description
FACTORY DEFAULTS SELECT
SP120 AC Drive Installation and Operation
RESTART MODE SELECT
]). If your drive is a K version,
] to