2.4.3 Branch Circuit Protection Devices

2.4.4 Input Power Conditioning

Installing and Wiring the Drive
The following table shows the minimum recommended values for the branch circuit
protection devices:
Fuse Rating (Class J)
Model
Single-Phase
S12-101P4LU
10A
S12-102P6LU
15 A
S12-104P0LU
20 A
S12-201P4LU
10 A
S12-202P6LU
10 A
S12-203P0LU
10 A
S12-204P0LU
15 A
S12-205P0LU
15 A
S12-207P1LU
20 A
S12-20010LU
30 A
S12-20015LU
N/A
S12-401P5LU
N/A
S12-402P5LU
N/A
S12-403P8LU
N/A
S12-405P5LU
N/A
S12-408P6LU
N/A
The drive is suitable for connection to input power within the rated voltage of the drive
(see specifications). The power factor of the input power supply must not exceed .99.
Compensation systems must ensure that overcompensation does not occur at any
time.
If the drive must be installed in any of the following conditions, a 3% impedance input
line reactor must be used:
line has intermittent noise spikes in excess of 2000 V
frequent voltage dips occur
the drive is operated on a generator
line has power factor correction capacitors
several drives are linked via a short common power supply bus bar
Table 2.2 – Branch Circuit Protection
Three-Phase
Single-Phase
N/A
140M-D8N-C10
N/A
140M-D8N-C16
N/A
140M-D8N-C25
10 A
140M-D8N-C10
10 A
140M-D8N-C10
10 A
140M-D8N-C10
15 A
140M-D8N-C16
15 A
140M-D8N-C16
15 A
140M-D8N-C16
20 A
140M-D8N-C25
30 A
3 A
6 A
10 A
10 A
15 A
English
Circuit Breaker Type
Three-Phase
N/A
N/A
N/A
140M-D8N-B40
140M-D8N-B63
140M-D8N-B63
140M-D8N-C10
140M-D8N-C10
140M-D8N-C16
140M-D8N-C16
N/A
140M-D8N-C25
N/A
140M-D8N-B25
N/A
140M-D8N-B40
N/A
140M-D8N-B63
N/A
140M-D8N-C10
N/A
140M-D8N-C16
2-5