Ferroli FORCE W 60 Instrucciones De Uso página 234

Ocultar thumbs Ver también para FORCE W 60:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Fault
Fault
code
F12
DHW sensor fault
F13
Fume sensor fault
F14
Delivery sensor 2 fault
F15
Fan fault
RESET button on con-
F26
troller on gas valve,
fault.
Supply voltage under
F34
170V
F35
Faulty mains frequency Electric mains trouble
Pressure switch con-
F37
tact open
F39
External probe fault
A41
Sensor positioning
A42
Heating sensor fault
Cascade temperature
F50
sensor fault
F52
Heating sensor fault
A61
Controller fault
No communication bet-
A62
ween controller and gas
valve
A63
A64
Controller fault
A65
F66
No communication bet-
F99
ween controller and dis-
play
234
Possible cause
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
No 230V power supply
Tachometric signal interrupted
Fan damaged
RESET button on controller fitted on gas valve
blocked or faulty.
Electric mains trouble
Low system pressure
Probe damaged or wiring shorted
Probe disconnected after activating the sliding tem-
perature
Delivery sensor disconnected from the pipe
Sensor damaged
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Controller internal error
Controller not connected
Valve damaged
Controller internal error
Wiring disconnected
cod. 3541Q760 - Rev. 00 - 02/2019
FORCE W
Cure
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the 3-pin connector wiring
Check the 5-pin connector wiring
Check the fan
Check the RESET button and replace the con-
troller on the gas valve if necessary.
Check the electrical system
Check the electrical system
Check the system water pressure
Check the wiring or replace the sensor
Reconnect the external probe or disable the sli-
ding temperature
Check the correct positioning and operation of
the heating sensor
Replace the sensor
Check the wiring or replace the sensor
Replace the sensor
Check the ground connection and replace the
controller if necessary.
Connect the controller to the gas valve
Replace the valve
Check the ground connection and replace the
controller if necessary
Check the wiring of the 6 wires between contro-
ller and display
EN
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Force w 80Force w 99Force w 120Force w 150Force w

Tabla de contenido