Ferroli JOLLY TOP I-VM Manual De Instalación Y Funcionamiento página 39

Fancoil tipo mueble con motor inverter/fancoil tipo mueble con selector de 3 velocidades
Idiomas disponibles
  • ES

Idiomas disponibles

The grounding wire in the electrical control box needs to be longer than the current-carrying wire.
Refer to Table 5-2 and Table 5-3 for the specifications of the power cord and communication wire. A wiring capacity that is too small will cause
the electrical wiring to become too hot, and result in accidents when the unit burns and becomes damaged.
Select the wire diameters (minimum value) individually for each unit based on Table 5-3.
The maximum allowable voltage range variation between phases is 2%.
Select the circuit breaker that has a contact separation of no less than 3 mm in all poles to provide full disconnection.MFA is used to select the
current circuit breakers and residual current operation breakers:
Model
Power
supply
Communication wire between
IDU and wired controller *
CIRCUIT BREAKER/FUSE (A)
Rated current of appliance(A)
≤3
>3 and ≤6
>6 and ≤10
>10 and ≤16
>16 and ≤25
>25 and ≤32
>32 and ≤50
>50 and ≤63
Figure 5-22 Wiring diagram (version 3V-VM; 3V-VN)
Table 5-2
Phase
Volt and frequency
Please refer to the corresponding wired controller manual for the wired
controller wiring.
AC FAN
FAN
TERMINAL BLOCK
1
2
3
4
5
To Thermostat
ALL
1-phase
220-240V~50/60Hz
Shielded
×AWG16-AWG18
15/15
Table 5-3
Nominal cross-sectional area (mm
Flexible cords
0.5 and 0.75
0.75 and 1
1 and 1.5
1.5 and 2.5
2.5 and 4
4 and 6
6 and 10
10 and 16
15
)
2
Cable for fixed wiring
1 and 2.5
1 and 2.5
1 and 2.5
1.5 and 4
2.5 and 6
4 and 10
6 and 16
10 and 25
loading