SPLIT 1X1
AROMA 2E
Flare form
Img. 6.4
8. Remove the flaring tool and form and then
inspect the end of the pipe for cracks and
even flaring.
Step 4: Connecting tubes
Connect the copper tubes to the indoor unit
first, and then connect them to the outdoor
unit. You need to connect the low pressure
pipes first and then the high pressure pipes.
1. When connecting the flare nuts, apply a
thin layer of refrigeration oil to the flare
ends of the pipes..
2. Align the center of the two tubes you are
going to connect.
3. Hand-tighten as much as possible
flare nut.
4. Using a wrench, tighten the nut on the
unit piping.
5. While holding the nut firmly, use a torque
wrench to tighten the flare nut according
to the torque values from Table 6.1.
Img. 6.7
6. Place the flaring tool on the shape.
7. Turn the handle of the flaring tool clockwise until the pipe is fully
flared. Flare the pipe with the dimensions indicated on the
Tabla 6.1.
Pipe
Tabla 6.1: Pipe Extension Beyond Form
NOTE: Use a wrench and torque wrench when connecting or
disconnecting pipes to/from the unit.
• Be sure to wrap insulation around the pipe, direct contact with bare
pipe may cause burns or frostbite.
• Make sure the tubing is properly connected. Overtightening can da-
mage the conical tube and undertightening can cause leaks.
6. REFRIGERANT TUBE CONNECTION
FLARING MEASUREMENT (A)
PRESSURE
TORQUE
GAUGE
MÍN
18-20 N·m
Ø6,4
8,3/0,3
(183-204 kgf·cm)
25-26 N·m
Ø9,5
12,4/0,48
(255-265 kgf·cm)
35-36 N·m
Ø12,7
15,4/0,6
(357-367 kgf·cm)
45-47 N·m
Ø15,9
18,6/0,7
(459-480 kgf·cm)
65-67 N·m
Ø19,1
22,9/0,9
(663-683 kgf·cm)
75-85 N·m
Ø22
27/1,06
(765-867 kgf·cm)
Indoor unit tubing
Img. 6.6
INSTALLATION MANUAL
(Unit: mm/pulg.)
FLARED
MÁX
8,3/0,3
12,4/0,48
15,4/0,6
Img. 6.5
19/0,74
23,3/0,91
27,3/1,07
Pipe
Flare nut
53