9. If a compressor is present, finish with its adjustment. The tank should be partly filled but the level should be below the ON
level. The setting is correct when an air bubble rises to the surface at regular intervals without the water level indicated on
the display changing. If the water level measured by the control box increases, the compressor is sending out too much air
and increasing the pressure in the pneumatic tube: the volume of air blown in must then be reduced by turning the regulator
dial in the other direction.
It is possible to test the control box without a pump:
1. Connect the control to a single-phase mains (connection of N and L1).
2. Set the motor current limits to 0.0 A.
3. Disable the phase error.
4. Bridge the control circuit TH2.
5. Deactivate the pump's thermal fault.
6. If the corresponding level sensors are connected, all program functions can be tested without connecting the pumps.
6. USE
IMPORTANT
The control box is equipped with an automatic key lock.
To set the lock settings, see 6.1.1 Keys.
6.1 PANEL AND OPERATING ELEMENTS
③
LCD display
6.1.1
Keys
Pressing
automatically after 2 minutes or if the
Except for monitoring the motor, no other program functions are active.
(MANUAL)
NOTE: When the ATEX mode is activated, the pump can only be started if the water level is above the OFF
level.
Pressing
The water level evaluation and the high water level alarm remain active but the pump motor is not switched
on if the ON level or the alarm level is reached.
The pump is switched according to the level measured by the selected sensor (see 6.2.1 Parameter settings).
All monitoring and safety functions are operated according to the saved settings.
- Pressing either of the two keys will move the menu to the previous or next menu, depending on the direction
indicated.
- When the menu is selected, these keys are used to change the setting values.
(SCROLL KEYS)
NOTE: Some modifications are only possible in STOP mode.
Pressing
Press
starts to flash.
(SELECTION/
Press
STOP)
Press
NOTE: The selected values remain in memory even when the unit is disconnected.
Temporary unlocking of keys
Press
during 3 seconds. An indication appears on the display, the keyboard is unlocked
Approximately 1 minute after the last actuation of any key, the keyboard gets relocked.
②
green LED indicating when the pump is operating
switches immediately the pump on. The operation LED lights up green. The pump stops
stops the pump motor immediately. The green LED turns off.
allows access to the parameter setting and viewing menus.
to enter the selected menu. Press
to select a value.
one last time: the value stops flashing, indicating that it is permanent.
button is pressed.
to enter the setting value modification: the value
21
①
Short travel keys