Managing the automatic key lock
- To deactivate the automatic keylock, choose "is deactivated" in the Keylock Menu.
- To activate the automatic keylock, choose "is deactivated" in the Service Menu then choose"is activated" in the Keylock Menu.
6.1.2 LED reporting
Green LED steady: pump running
Red LED steady: fault reported
6.1.3 Indications on the display
Normal operation
During operation of the control box:
Example 1:
level :
12 cm
P1 auto
level :
12 cm
P1 auto
Example 2:
level :
12 cm
SW12–HW =0 0 0
P1 auto
P1 pare
SW12–HW =0 0 0
P1 pare
SW12–HW =0 0 0
total pump hours
If the pump is running, the motor current and operating status are displayed alternately.
P1 pare
P1 0025
total pump hours
Alarm display
P1 0025
When an alarm occurs, the current alarm type is displayed (see 6.2.3 Warnings and alarm messages). The pump's LED turns red.
total pump hours
Therm. fault P1
P1 0025
Parameters settings
is deactivated
Therm. fault P1
level :
12 cm
When viewing the Menus, the screen displays:
P1 auto
is deactivated
Therm. fault P1
is deactivated
SW12–HW =0 0 0
P1 pare
Information retrieval
total pump hours
P1 0025
6.2 MENUS
Therm. fault P1
6.2.1 Parameter settings
is deactivated
The selection of a parameter and the modification of its value are possible with
The following table shows and explains the possible settings.
NOTE
For safety reasons, setting some parameters is only possible if the pump has been stopped manually (pressing
Upper line: Parameter
Base load OFF
Base load ON
High water
(HW)
run-time
(=running time)
- the upper line on the display indicates the water level measured by the pressure sensor (ex. 1) or the
switching status of the float switches (ex. 2 with SW1: OFF float, SW2: ON float, HW: Alarm float,
O: activated , 1: deactivated)
- the lower line indicates the operating status of the pump: Hand (the pump has been switched on
manually), Stop (the pump has been switched off manually) or Auto (the pump is switched on or off
depending on the level measurement).
- on the upper line, the parameter,
- on the lower line the selected value for the parameter.
The values can be changed by pressing
Values such as "maintenance interval", "total pump run time", "number of pump starts" can be displayed
and reset (see 6.2.2 Information retrieval).
The alarm log can also be viewed. It stores and displays the last 32 alarms. After this number, the backup
automatically deletes the oldest alert.
Lower line: Parameter value
Help to choose
XX cm
Choose the value such as
OFF level ≤ ON level
XX cm
Choose the value such as
OFF level ≤ ON level
XX cm
Choose the value such as
ON level < HW level
and HW level ≤ max value of level sensor
is deactivated
or value from 0 to 300 s
and
and
Pump stop level (OFF Level).
NOTE: Modification possible only if the pump has been
stopped manually (pressing
Pump activation level (ON Level).
NOTE: Modification possible only if the pump has been
stopped manually (pressing
Alarm level.
NOTE: Modification possible only if the pump has been
stopped manually(pressing
Maximum pump running time: When the pump is operating,
it stops briefly after the selected time.
This function is used to check whether the pump is
emptying the tank within the normal running time.
After 3 consecutive interruptions, the alarm message
"Time" appears. The pump is stopped and it is necessary to
reset the alarm to restart the pump.
Selecting "is deactivated" means that the pump will only be
stopped when the OFF level is reached.
This function can be used to remove the air accumulated
in the pump and thus start the liquid flowing back again.
To do this, select a time that is significantly longer than the
normal draining time: the pump will stop briefly if it has
not managed to lower the water level below the OFF level
point during the set time.
NOTE: The factory setting is 60 s.