Hitachi HC-A8MB Manual De Instalación Y Funcionamiento página 89

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
FONCTIONNEMENT
Offset
Description
167
Numéro d'alarme
168
Température de refoulement R134a
169
Température d'aspiration R134a
170
Pression de refoulement R134a
171
Pression d'aspiration R134a
172
Fréquence de compresseur R134a
Ouverture de la soupape de sécurité
173
intérieur R134a
174
Valeur actuelle du compresseur R134a
175
Code de nouvel essai R134a
176
R134 Te SH
177
R134 Secondary Current
178
R134 Stop Code
179~
189
190
YCC - Enabled Units
191
YCC - Working Units
192
YCC - Required Units
?
N O T E
Register address is calculated as: 5000+(Modbus_Id*200)+offset
Modbus_Id as configured by configuration software
For VRF / Package units, only the relevant data are available (heating units registers will not give any value). The situation is the same for heating
units (registers related to air/air units will not give any value).
• Availability:
PAC: VRF and package units.
-
-
RAC: Domestic units connected to the H-link via PSC-6RAD or SPX-RAMHLK
-
ATW: Air to water units.
• (1) Take into account only if it is different from zero.
(2) Bit 0 (ON/OFF) and Bit 4 (Louver) selectable only when all centrals are actived.
In order to full lock setting from RCS (Central shown in RCS) set this register to 31
83
PMML0351A rev.4 - 04/2020
Valeurs
Lecture/Écriture
0: Alarm
XXX: Alarm number
Réservées
0~8
0~8
0~8
Disponibilité
VRF
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
Lecture
RAC
ATW
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O