OPERATION
Offset (1)
Description
22
Unit operation condition
23
(Not used)
24
Ambient temperature (2)
Remote control switch temperature
25
(only when available in the unit) (2)
26
Remote control switch configuration
27
Remote control switch group
28~30
(Not used)
31
Remote sensor temperature (2)
?
N O T E
•
(1) Register address is calculated as: "N + (Address * 32) + Offset" where:
•
N : Data table position is 2000, position 20000 is also available to maintain compatibility with old Modbus gateway.
•
A ddress: Indoor unit address as configured by configuration software.
•
(2) These numbers refer to signed 16-bit value using 2-complement format for negative values
•
(3) Bit 0 (ON/OFF) and Bit 4 (Louver) selectable only when all centrals are actived.
•
In order to full lock setting from RCS (Central shown in RCS) set this register to 31.
10
PMML0351A rev.4 - 04/2020
Values
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
(Not used)
-63ºC ~ 63ºC
-63ºC ~ 63ºC
b0: 0 Master/1Slave
b1: 0 wih RCS/1 Without RCS
0: No group
1~255
(Not used)
-63ºC ~ 63ºC
Read/Write
Read
(Not used)
Read
Read
Read/Write
Read/Write
(Not used)
Read