DRIFT
5.3 UTOMHUSENHETER
Some state registers about outdoor unit have been added. Using these registers it is now possible to know the status of the refrigerant
cycle. Some control registers have also been added.
Offset
0
1
Compressor Discharge Temperature
2
Heating Evaporating Temperature
3
Number of operating Compressor
4
5
6
7
8
9
10
11
Outdoor Unit Option Enabled
12
13
14
15
16
17
Power Level Current Value
18
?
N O T E
•
Register address is calculated as: 5000+(Modbus_Id*200)+offset
•
Modbus_Id as configured by configuration software
194
PMML0351A rev.4 - 04/2020
Beskrivning
Outdoor Air Temperature
Utloppstryck
Sugtryck
Total Current
Total Real Frequency
EVO1
EVO2 / Hot Bypass
EVB
Noise Control Enabled
Noise Control Level Set
Power Control Enabled
Power Level
Power Level Set
Power Control Possible
Värden
-63ºC ~ 63ºC
0 ~ 200 ºC
0.0 ~ 5.0 MPa (0.1 MPa)
-0.2 ~2.0MPa (0.1 MPa or 0.01MPa depending
unit)
0 ~ 255 A
0 ~ 255 Hz
0 ~ 100 %
0 ~ 100 %
0 ~ 100 %
0: Disable
1: Enable (it's possible to use the following
options, also if the value of register 16 "Power
Level Set" is 1)
0: Disable
1: Enable (it's possible to send the noise level)
0~9 (See the service manual of Outdoor unit,
function db)
0: Disable
1: Enable (it's possible to send the power level)
0~100%
0~100%
0~100%
0: Not possible
1: Possible
Läs/skriv
Läs
Läs
Läs
Läs
Läs
Läs
Läs
Läs
Läs
Läs
Läs
Läs/skriv
Läs/skriv
Läs/skriv
Läs/skriv
Läs/skriv
Läs
Läs
Läs