Hitachi HC-A8MB Manual De Instalación Y Funcionamiento página 154

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
DRIFT
Offset
Beskrivelse
147
Software LCD
148
Enhedens kapacitet
149
Unit Power Consumption
150
Water Outler HP (TwoHP)
Ta1av: Outdoor Unit Ambient Average
151
Temperature
Ta2: Second Ambient Temperature
152
Ta2av: Second Ambient Temperature
153
154
O2: Water outlet Temp 2 (Two2)
155
O3: Water outlet Temp 3 (Two3)
156
Tg: Gas Temperature (THMg)
157
Tl: Liquid Temperature (THMl)
158
EVI: Indoor expansion valve openning
159
CD: Capacity Data
160
Mixing Valve Opening
161
Afrimning
162
Enhedsmodel
163
Th: Water Temp Setting (Ttwo)
164
Vandgennemstrømning
165
Pump Speed
166
Systemstatus 2
148
PMML0351A rev.4 - 04/2020
0~100 kun YUTAKI S &
(inst)
(avg)
0: No defrosting
1: Defrosting
0: Yutaki S
1: Yutaki SC
2: Yutaki S80
3: Yutaki M
4: Yutaki SC Lite (New)
5: Yutampo (New)
6: YCC (New)
Water Flow [0.1m3/h]
Bit 0: Defrost
Bit 1: Solar
Bit 2: Water Pump 1
Bit 3: Water Pump 2
Bit 4: Water Pump 3
Bit 5: Compressor ON
Bit 6: Boiler ON
Bit 7: DHW Heater
Bit 8: Space Heater
Bit 9: Smart function
input enabled
Bit10: Forced OFF
Bit11: DHW recirculation
Pump State
Bit12: Solar Pump
Output State
Værdier
Læs/Skriv
Læs
Læs
Læs
Læs
S Combi
-80~100
Læs
-80~100
Læs
-80~100
-80~100
Læs
-80~100
Læs
-80~100
Læs
-80~100
Læs
0~100
Læs
Læs
0~100
Læs
Læs
Læs
-80~100
Læs
Læs
0~100
Læs
Læs
Availability
VRF
RAC-
ATW
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
loading

Este manual también es adecuado para:

Hc-a16mbHc-a64mbHc-a64net