DRIFT
Offset
Beskrivelse
167
Alarmnummer
168
Udladningstemperatur R134a
169
Sugetemperatur R134a
170
R134a udladningstryk
171
R134a sugetryk
172
Kompressorfrekvens R134a
Indendørs ekspansionsventilåbning
173
R134a
174
Kompressor nuværende værdi R134a
175
Genforsøgskode R134a
176
R134 Te SH
177
R134 Secondary Current
178
R134 Stop Code
179~
189
190
YCC - Enabled Units
191
YCC - Working Units
192
YCC - Required Units
?
N O T E
Register address is calculated as: 5000+(Modbus_Id*200)+offset
Modbus_Id as configured by configuration software
For VRF / Package units, only the relevant data are available (heating units registers will not give any value). The situation is the same for heating
units (registers related to air/air units will not give any value).
• Availability:
PAC: VRF and package units.
-
-
RAC: Domestic units connected to the H-link via PSC-6RAD or SPX-RAMHLK
-
ATW: Air to water units.
(1) Take into account only if it is different from zero.
(2) Bit 0 (ON/OFF) and Bit 4 (Louver) selectable only when all centrals are actived.
In order to full lock setting from RCS (Central shown in RCS) set this register to 31
149
PMML0351A rev.4 - 04/2020
Værdier
Læs/Skriv
0: Alarm
XXX: Alarm number
Reserveret
0~8
0~8
0~8
Availability
VRF
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
Læs
RAC-
ATW
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O