Hitachi HC-A8MB Manual De Instalación Y Funcionamiento página 15

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
OPERATION
5.2 INDOOR UNITS
5.2.1 Available data for HC-A(8/16/64)MB
Offset (1)
Description
0
Exist
1
System address
2
Unit address
3
On/Off setting order
4
Mode setting order
5
Fan setting order
6
Setting temperature
7
Louver setting
8
Central setting (3)
9
On/Off status
10
Mode status
11
Fan status
12
Setting temperature status
13
Louver status
14
(Not used)
15
Inlet temperature reading (2)
16
Outlet temperature reading (2)
17
Gas pipe temperature reading (2)
18
Liquid pipe temperature reading (2)
19
Alarm code
20
Compressor stop cause
21
Indoor unit expansion valve opening
9
PMML0351A rev.4 - 04/2020
Values
0: No exist
1: Exist
0~63
0: Stop
1: Run
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
0: Low
1: Medium
2: High
3: High2
4: Auto
ºC (set according to the unit working range)
0 ~ 7 (7 is Auto)
Bit 0: On/Off (always can be stopped)
Bit 1: Mode
Bit 2: Setting Temp
Bit 3: Fan
Bit 4: Louver
0: Off
1: On
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
0: Low
1: Medium
2: High
3: High2
4: Auto
ºC (set according to the unit working range)
0 ~ 7 (7 is Auto)
(Not used)
-63ºC ~ 63ºC
-63ºC ~ 63ºC
-63ºC ~ 63ºC
-63ºC ~ 63ºC
Alarm unit from 7-segment
(Read unit service manual)
0~100
Read/Write
Read
Read
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read
Read
(Not used)
Read
Read
Read
Read
Read
Read
Read
loading

Este manual también es adecuado para:

Hc-a16mbHc-a64mbHc-a64net