- Switch off the UPS.
- Unplug the input cord from the mains socket.
Step 1 - Using a Phillips head screwdriver, remove the four black screws located on the sides of the
UPS.
Step 2 - Place the front plate on the top of the UPS for easy access to the battery connections.
Step 3 - Disconnect the red connector from the battery pack.
Step 4 - Using a Phillips head screwdriver, remove the sliver screws from the silver battery pack retaining
plate (the KEOR SPE 750-1000 have two screws, the KEOR SPE 1500-2000-3000 have four screws)
Step 5 - Pull on the transparent tab to slide the battery pack out of the UPS.
6.2
Battery information
Model
750 VA
1000 VA
1500 VA
2000 VA
3000 VA
Battery source 1
2 PCS Minhua type MS7-12
2 PCS Minhua type MS9-12
3 PCS Minhua type MS9-12
4 PCS Minhua type MS9-12
4 PCS Minhua type MS9-12
KEOR TOWER SPE
Installation and User Manual
Battery source 2
2 PCS Ritar type RT1270
2 PCS Ritar type RT1290
3 PCS Ritar type RT1290
4 PCS Ritar type RT1290
4 PCS Ritar type RT1290EP