Supply voltage:
Motor protection:
Degree of protection:
Winding class:
Temperature class:
Ambient temperature:
Media temperature:
Minimum pressure
at 500m altitude:
Pression de service nécessaire: 10 bar
Noise:
Leakage current:
english
10. Specifications
1×230 V +6/-10%, 50 Hz
No external motor protection is necessary
IP 44
Classe d'isolation F
TF 110
max. 40 °C
+2 °C to 95 °C, for short periods (ca. 30 min) 110 °C
The temperature of the medium must be higher
than the ambient temperature to prevent condensation water
from forming in the terminal box and the stator.
Ambient temperature
°C
0
10
20
30
35
40
It is recommended to keep the temperature
Warning
below 65 °C in drinking water installations
to prevent the danger of lime deposits.
up to 75 °C water temperature
at 90 °C water temperature
at 110 °C water temperature
For every ±100 m altitude
sound pressure level under 54 dB(A)
The power line filter of the pump causes a leakage current
to the ground wire of less than 3.5 mA during operation.
11. Disposal
This product and the special electronic components (lead-free)
must be disposed of in accordance with the environmental
regulations.
Media temperature
Min. °C
Max. °C
2
110
10
110
20
110
30
110