・Power cable size and device capacity
MOP is used to select the fuse, switch, or breaker for current leakage.
Outdoor unit model
Unit combination
TURYH0723AN40AN
TURYH0963AN40AN
TURYH1203AN40AN
TURYH0723AN40AN
TURYH1443BN40AN
TURYH0723AN40AN
TURYH0963AN40AN
TURYH1923BN40AN
TURYH0963AN40AN
TURYH1203AN40AN
TURYH2403BN40AN
TURYH1203AN40AN
TURYH0724AN40AN
TURYH0964AN40AN
TURYH1204AN40AN
TURYH0724AN40AN
TURYH1444BN40AN
TURYH0724AN40AN
TURYH0964AN40AN
TURYH1924BN40AN
TURYH0964AN40AN
TURYH1204AN40AN
TURYH2404BN40AN
TURYH1204AN40AN
・The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one size thicker in diameter. Make sure the
power-supply voltage does not drop more than 10%. Make sure that the voltage imbalance between the phases is 2% or less.
・Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 245 IEC57).
For example, use wiring such as YZW.
10-3. Control cable specifications
・Transmission cable
Type
2-core shielded cable CVVS, CPEVS, or MVVS
Size
1.25 mm
(AWG 16)
2
Length
Max. 200 m (656 ft)
The maximum allowable length of transmission cables via outdoor units (both centralized control transmission cables and indoor-outdoor transmission cables) is
Remarks
500 m (1640 ft).
The maximum allowable length of transmission cables from the power supply unit to each outdoor unit or to the system controller is 200 m (656 ft).
* Do not use a single multiple-core cable to connect indoor units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and
malfunctions.
* Ensure shield continuity when extending the transmission cable.
・Remote controller cable
Type
Size
Max. 10 m (32 ft)
Length
* If the length exceeds 10 m (32 ft), use a 1.25 mm
cable.
WT09117X05
Minimum size [mm
Power cable
208 V
230 V
21.2 (4)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
13.3 (6)
21.2 (4)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
8.4 (8)
8.4 (8)
ME remote controller cable
2-core sheathed cable (unshielded) CVV
0.3–1.25 mm
(AWG 22–16) (0.75–1.25 mm
2
(AWG 16) shielded
2
(AWG)]
2
Earth wire
208 V
230 V
21.2 (4)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
13.3 (6)
21.2 (4)
13.3 (6)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
21.2 (4)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
5.3 (10)
8.4 (8)
8.4 (8)
8.4 (8)
8.4 (8)
MA remote controller cable
(AWG 18–16) if a simple remote controller is connected)
2
Max. 200 m (656 ft)
GB-31
MCA (A)
MOP (A)
38/35
60/50
44/40
70/60
47/44
70/60
38/35
60/50
38/35
60/50
44/40
70/60
44/40
70/60
47/44
70/60
47/44
70/60
17
25
20
30
21
35
17
25
17
25
20
30
20
30
21
35
21
35