Connection of the motors with preassembled cables

Carry out the wiring in accordance with the valid standards and regulations.
Only use Kollmorgen preassembled shielded cables for the resolver and power con-
nections.
Incorrectly installed shielding leads to EMC interference and has an adverse effect
on system function.
The maximum cable length is defined in the instructions manual of the used servo
amplifier.
For a detailed description of preassembled cables, please refer to the regional accesso-
ries manual.
14.3

Guide for electrical installation

Check that the servo amplifier and motor match each other. Compare the rated vol-
tage and rated current of the unit. Carry out the wiring according to the wiring dia-
gram in the instructions manual of the servo amplifier. The connections to the motor
are shown in chapter "Connector Pinout" from p.131.
Install all cables carrying a heavy current with an adequate cross-section, as per EN
60204. The recommended cross-section can be found in the Technical data.
In case of long motor cables (>25m) and dependent on the type of the used servo ampli-
fier a motor choke (3YL or 3YLN) must be switched into the motor cable (see instructions
manual of the servo amplifier and accessory manual).
Ensure that there is proper earthing of the servo amplifier and the motor. Use correct
earthing and EMC-shielding according to the instructions manual of the servo ampli-
fier which is used. Earth the mounting plate and motor casing.
If a motor power cable is used which includes integral brake control leads, then the-
se brake control leads must be shielded. The shielding must be connected at both
ends (see instructions manual of the servo amplifier).
Cabling:
Connect up all shielding via a wide surface-area contact (low impedance) and me-
tallized connector housings or EMC-cable glands.
Requirements to cable material:
Capacity
Motor cable
Resolver cable
Servomotors AKM
04/2013
Route power cables as separately as possible from control cables
Connect up the resolver or encoder.
Connect the motor cables, install motor chokes close to the amplifier
Connect shields to shielding terminals or EMC connectors at both ends
Connect the holding brake, if used
Connect shielding at both ends.
less than 150 pF/m
less than 120 pF/m
Electrical Installation