WIKA GDM-100-TI Manual De Instrucciones página 14

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

5. Commissioning, operation
5.2.1 Limit values for the contact load with resistive load
Maximum rated operating
EN
voltage Ueff
Rated operating current
Switch-on current
Switch-off current
Continuous current
Maximum switching power
Do not exceed the limit values. In order to permanently ensure safe operation, the
following load values are recommended:
Voltage
(per IEC 38)
DC/AC
230 V
110 V
48 V
24 V
The switching current must not be less than 20 mA with low voltages for switching relia-
bility reasons.
Overcurrent protectors
The instruments do not provide for incorporated overcurrent protectors. Should protec-
tors be required, the following values in accordance with EN 60 947-5-1 are to be
recommended.
Voltage 24 V: 2 A
Voltage 250 V: 1 A
14
gas-filled instruments
AC 250 V
1 A
1 A
0.6 A
30 W, 50 VA
gas-filled instruments
resistive load
DC
AC
100 mA
120 mA
200 mA
240 mA
300 mA
450 mA
400 mA
600 mA
For higher loads, and for instruments with liquid-filled cases, WIKA model
905.1X contact protection relays are recommended
WIKA operating instructions, models GDM-100-TI, GDM-100-TA
liquid-filled instruments
inductive
resistive load
load
cos ϕ >0.7
DC
65 mA
65 mA
130 mA
130 mA
200 mA
190 mA
250 mA
250 mA
liquid-filled instruments
AC 250 V
1 A
1 A
0.6 A
20 W, 20 VA
inductive load
AC
cos ϕ >0.7
90 mA
40 mA
180 mA
85 mA
330 mA
130 mA
450 mA
150 mA
Tabla de contenido
loading

Este manual también es adecuado para:

Gdm-100-ta

Tabla de contenido