Stiebel Eltron HSBC 180 Plus Operación E Instalación página 37

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 148
INSTALLATIoN
electrical connection
11.5.1 Filling the heating system
Note
Fill the heating system exclusively via the lower drain &
fill valve on the buffer cylinder.
In the delivered condition, the 3-way diverter valve of the mul-
tifunction assembly is in its centre position, so that the heating
circuit and the heat exchanger for DHW heating are filled evenly.
When power is switched on, the 3-way diverter valve automatically
switches to heating mode.
To fill or drain the system later, you must first place the 3-way
diverter valve into its centre position.
To set the heat pump manager:
f With the MENU key, call up the main menu.
f Select the menu or value and confirm with OK:
DIAGNOSIS
RELAY TEST SYSTEM

DRAIN HYD
f Fill the heating system via the lower drain & fill valve on the
buffer cylinder.
f Vent the pipework.
11.5.2 DHW cylinder filling
f Fill the DHW cylinder via the cold water connection.
f Open all downstream draw-off valves until the appliance is
full and the pipework is free of air.
f Adjust the flow rate. For this, observe the maximum permis-
sible flow rate with a fully opened tap (see chapter "Specifi-
cation / Data table"). If necessary reduce the flow rate at the
butterfly valve of the safety assembly.
f Carry out a tightness check.
f Check the safety valve.
www.stiebel-eltron.com
11.6 Venting the appliance
2
1 Air vent valve
2 PCB
f Vent the pipework and indirect coil by pulling up the red cap
on the air vent valves.
f Close the air vent valves after the venting process.
Material losses
!
Close the air vent valves again after venting.
12. Electrical connection
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with relevant regulations.
f Before any work on the appliance, disconnect all
poles from the power supply.
WARNING Electrocution
The connection to the power supply must be in the form
of a permanent connection. Ensure the appliance can be
separated from the power supply by an isolator that dis-
connects all poles with at least 3 mm contact separation.
This requirement can be met by using contactors, circuit
breakers, fuses/MCBs, etc.
Material losses
!
Provide separate fuses for the two power circuits of the
appliance and the control unit.
Material losses
!
Provide separate fuses/MCBs for the two power circuits,
i.e. for the compressor and the electric emergency/boost-
er heater circuits.
Material losses
!
Observe the type plate. The specified voltage must match
the mains power supply.
Note
You must have permission to connect the appliance from
the relevant power supply utility.
HSBC 180 Plus | HSBC 180 S Plus |
1
1
37
loading

Este manual también es adecuado para:

Hsbc 180 s plus