Never use the generator without an air filter, with a
damaged or incorrectly installed filter. If this
happens, dust intake to the engine will occur, causing rapid
breakdowns. This type of damage is not covered by the
distributor's warranty.
1. Remove the bolts, then remove the access cover (7);
2. Loosen the wing nut and remove the air filter cover;
3. Loosen the fixing nut and remove the filter element;
4. Blow with compressed air until it is completely clean. If
it is very dirty, wash it with water and let it dry
completely;
5. Fit the filter element and assemble the other
components in the reverse order of disassembly.
2.
Using a clogged and dirty filter will restrict the air
flow in the carburetor affecting the generator
performance.
1. Loosen the fixing bolt of the filter cover;
2. Remove the fuel filter (13) and blow it out with
compressed air until it is completely clean;
3. Fit the clean filter and tighten the bolt.
1.
1. Empty the fuel tank;
2. Loosen the tightening clamps to release the filter from
the fuel hoses;
3. Remove the clogged filter and replace with a new one;
4. Fit the clamps.
Fuel filter
Check the direction of fuel flow, represented by an
arrow on the filter.
3.
2.
Clamps
Do not loosen or adjust the speed limiting bolt (22) as this
may alter the performance and reduce the service life of the
motor, as well as damaging the AVR (automatic voltage
regulator).
This will cause the loss of warranty on the equipment.
If the operating speed is not correct, the AVR will produce
a forced excitation. Operation under such conditions for a
long period of time will damage the AVR.
Speed limiting bolt
Preparing storage for long periods is vital to avoid problems
and increase the useful life of the generator.
Storage
Never store the equipment with diesel in the tank.
Depending on the region and storage conditions, diesel can
deteriorate and oxidize, causing damages in the carburettor
and fuel system, difficult starts and clogging caused by
particle accumulation.
If you have stored the machine with diesel on the tank, to
avoid
difficult
start-ups,
recommendations below considering the previous storage
period:
Less than 1 month:
▪ Follow the usual procedure.
1 month to 1 year:
▪ Drain all diesel from the fuel tank;
▪ Run the engine until it stops due to lack of fuel.
Over 1 year:
▪ Drain all diesel from the fuel tank;
▪ Run the engine until it stops due to lack of fuel;
▪ Change the oil.
Cleaning
Clean the generator after each use. Careful handling
protects the generator and extends its service life.
please
follow
the
loading