Ditel JR-C Manual Tecnico página 55

Idiomas disponibles

Idiomas disponibles

mV input
SCAL
tEAC
InP1
0000
dSP1
0000
00.00
InP2
0000
dSP2
0000
NOTE:
Display configuration/scaling is independent to stored TARA value present in memory. It only must be
considered that, once this configuration is finished, display reading will be affected by that TARE value.
FiLt
0
SERIE KOSMOS
For both display scaling "SCAL" and "tEAC" methods, parameters to be
sequentially introduced are identical.
It only must be considered that in "SCAL" method, all values must be
manually introduced through the three frontal keys whereas in "tEAC"
method, input signal value must be present at the conector at each
point that is intended to be configured.
FIRST POINT INPUT AND DISPLAY VALUE:
InP1:
Input value indication.
0000:
Value entering in counts within available model display range.
dSP1:
Display value indication.
0000:
Value entering in counts within available model display range.
DECIMAL POINT:
00.00:
Setting of decimal point position.
(Decimal point can be located in any position, and will be
the same for Display 1 and Display 2. This position remains
fixed for all configuration steps and also for RUN mode).
SECOND POINT INPUT AND DISPLAY VALUE:
InP2:
Input value indication.
0000:
Value entering in counts within available model display range.
dSP2:
Display value indication.
0000:
Value entering in counts within available model display range.
WEIGHTED AVERAGE FILTER:
FiLt:
0 to 8 Configurable
www.ditel.es
JR-C / JR20-C
Value Fc (Hz)
Value
Fc (Hz)
0
--
5
0.35
1
1.20
6
0.29
2
0.44
7
0.23
3
0.41
8
0.18
4
0.38
55
loading

Este manual también es adecuado para:

Jr20-c