Ferroli ENERGY TOP B Serie Instrucciones De Uso, Instalación Y Mantenimiento página 65

Ocultar thumbs Ver también para ENERGY TOP B Serie:
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
ENERGY TOP B
To connect a single module
After establishing on which side of the module to make the water and gas connec-
tions, connect the flanges with the joining section contained in the kit on that side
after suitably welding them to the system pipes. Make sure to correctly fit the special
seals contained in the kit.
Connect a Ø40 pipe to the condensate drain pipe for removing the condensate pro-
duced during operation (see fig. 48).
Fit the blind flanges contained in the kit on the opposite side of the module, placing
the special seals in between.
5
1
Gas inlet
2
System delivery
3
System return
4
Condensate drain
5
Blind flanges - kit 042027X0 (optional)
7
Blind flanges - kit 042027X0 (optional)
To connect several modules in line
Connect the first module to the system and gas pipes, as described above, but with-
out fitting the blind flanges on the opposite side of the module to that of the connec-
tion.
Connect the second module on this side, making sure to align the connection flang-
es and the condensate drain pipe. Place the seals contained in the kit between the
flanges of the two modules.
Fit the bolts contained in the kit on the flanges from the inside of the first module,
making them come out of the flanges in the second module. Partially tighten the nuts
on the bolts from inside the second module.
Before tightening the nuts, make sure all the seals are correctly positioned and fit
the condensate drain pipes of the two modules (see fig. 49).
Tighten the nuts and repeat the connection operations for the following modules.
5
8
1
Gas inlet
2
System delivery
3
System return
4
Condensate drain
5
Blind flanges - kit 042027X0 (optional)
7
Blind flanges - kit 042027X0 (optional)
8
Seals and screws (standard)
2
1
3
7
4
fig. 19
2
1
3
7
fig. 20
cod. 3541G011 - Rev. 00 - 07/2015
To connect several opposed modules
Optional kit code 042026X0 is available for connecting the water and gas manifolds in
series. The kit contains 3 flanged "U" pipes.
2
1
3
fig. 21 - Kit for connection of opposed modules
A
1st Module
B
2nd Module
C
3rd Module
D
4th Module
1
Gas inlet
2
System delivery
3
System return
5
Blind flanges
7
Drilled flanges
8
Seals and screws (standard)
Arrange the modules according to the layout of fig. 21.
Connect the first module to the system and gas pipes using the flanges with pipe
section and respective seals contained in the kit 042027X0.
Position the second module, making sure to align the connection flanges and the con-
densate drain pipe. Fit the seals (supplied) between the flanges of the two modules.
Fit the bolts (supplied) on the flanges from inside the first module, making them
come out the flanges in the second module. Partially tighten the nuts on the bolts
from inside the second module.
Before tightening the nuts, make sure all the seals are correctly positioned and fit
2
the condensate drain pipes of the two modules (see fig. 49).
Tighten the nuts and repeat the connection operations for the "U" pipes and next
1
modules. Fit the blind flanges contained in the kit 042027X0 on the last module.
Safety device and separator module (optional)
3
The Safety Device and Separator Module for series ENERGY TOP Bmodular gener-
4
ators is an ISPESL certified module containing a hydraulic separator and safety, protec-
tion and control devices required by file "R" section R3A and R3B, intended for use with
series ENERGY TOP Bmodular generators .
Every ISPESL Safety Device Module comprises a cabinet of the same size and appear-
ance as the modular generators ENERGY TOP B, containing a hydraulic separator with
air valve and thermal insulation, the respective system delivery and return manifolds, a
gas manifold, and a discharge manifold for the safety valve. The safety devices required
by file "R" section R3A and R3B are fitted on the hydraulic manifolds and hydraulic sep-
arator body. Provision is also made for the probe pocket of a possible fuel shutoff valve,
to be installed in the system , on the outside of the bank of modules.
The hydraulic separator contained in the module allows the hydraulic circuit of the mod-
ules ENERGY TOP B (primary circuit) to be made independent of the hydraulic circuit of
the respective heating system (secondary circuit). The separator is sized for correct op-
eration up to 1000 kW, and the main advantages offered are:
An external circulating pump for the primary circuit is not necessary. In fact, circula-
tion in the primary circuit is ensured by the circulating pumps contained inside the
generators ENERGY TOP B.
When the secondary pump is deactivated, also the circulation in the system circuit
stops; the entire flow delivered by the circulating pumps contained inside the gener-
ators ENERGY TOP B is bypassed through the hydraulic separator.
The flow in the primary circuit can remain constant, whereas the secondary circuit
can function with a variable or intermittent flow rate.
There are no anomalous operating conditions in which the system pumps interact
with the circulating pumps in side the generators ENERGY TOP B, creating unwant-
ed head and flow-rate variations in the circuits.
Sizing of the system circulating pump can be carried out according to the needs of
just the secondary circuit.
8
C
D
B
A
1
2 - 3
7
EN
2
1
3
1
2
3
5
65
loading