Brightness-based function:
If the brightness-based function is activated, the basic light
state is no longer left when there is no one present.
The desired light output for the basic light is set with the
dimming level.
If the amount of daylight exceeds the response threshold,
the basic light is switched off.
If the amount of daylight falls below the response thresh-
old, the basic light is automatically switched on again.
Time-based function:
If the time-based function is activated, the basic light
stay-ON time setting can be used to set how long the
basic light should be active.
After the stay-ON time has elapsed, the basic light state is
left and the lighting is switched off.
The desired light output for the basic light is set with the
dimming level.
Fixed constant light control/dynamic constant light
control
With fixed constant light control, the sensor does not save
a manual override of constant light control by a button.
With dynamic constant light control, on the other hand, the
new brightness is set as the new control threshold.
In the case of manual override without constant light
control activated in dynamic constant light control mode,
the current light level is set as the new value for "Main light
dimming".
Button input
Buttons can be integrated and configured via the STEINEL
Connect app.
In order to be able to configure a button via input S,
the product to which the button is connected must be
assigned to a group.